EasyManua.ls Logo

Eaton FD120 - Wiring and Connection Guidelines; Control Wiring Specifications; Battery Connection Wiring

Eaton FD120
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
O & M Manual IM05805019K-002 EATON Diesel Plus
Effective April 2015 Diesel Engine Fire Pump Controller
28 EATON INDUSTRIES CANADA COMPANY www.chfire.com
APPENDIX K:
For control wiring, use #14 AWG wire for all electrical
connections except battery connections.
For battery connection, terminals 6, 7, 8 and 11, use the
following:
#10 AWG: 0' to 25' (7.62 m)
# 8 AWG: 25' to 50' (15.2 m)

Table of Contents