EATON Diesel Plus O & M Manual IM05805019K-002
Diesel Engine Fire Pump Controller
Effective April 2015
EATON INDUSTRIES CANADA COMPANY www.chfire.com 31
9.3 Engine Test
To run a manual test, depress the "Engine Test" button on the
keypad. Then press ACK. The Drain Valve Solenoid will energize
and drop the pressure on the controller to zero. The controller
will start the engine automatically. The “Engine Run
annunciator will illuminate.
Press the STOP pushbutton.
The engine will stop.
NOTE
Engine will shutdown if Low Oil Pressure, High Water Temp or Overspeed
alarms are detected during the engine test.
9.4 Weekly Exerciser Test
Turn the mode selector switch to the “OFF” position.
To test the Weekly Exerciser, preprogram the controller to
initiate the test at a time suitable to the user.
Turn the mode selector switch to the “AUTO” position.
At the programmed time and date the drain valve solenoid will
open. The Engine will crank and start. The “Engine Run”
annunciator will illuminate.and the drain valve solenoid will
close.
Press the STOP pushbutton.
The engine will stop.
Reprogram Weekly Exerciser for normal operation.