Engine Board Terminal Blocks
Field Connections
Diesel Plus Foam Pump Controller
Technical Data TD081022EN
E ective April 2015
Inputs
Outputs
7HFKQLFDO'DWDDQG6SHFLᚏFDWLRQV
/LQH7HUPLQDOV,QFRPLQJ&DEOHV
Recommended Wire Size Terminal Number Distance
I/O Board
Stranded # 14 (1.63mm)
Stranded # 14 (1.63mm)
11, 34-39, 60-95
Option Board Terminals
N. A.
N. A.
Engine Board
Stranded # 14 (1.63mm)
1-5, 9, 10, 12, 301, 302, 303, 304, 310, 311, 312
L, N, G
N. A.
Battery Wire
Stranded # 10 (2.59mm)
Stranded # 8 (3.26mm)
6, 8, 11
6, 8, 11
0 feet to 25 feet (7.62m)
25 feet to 50 feet (7.62-15.24m)
Field Connections
BATTERY #1 INPUT(+)
FUEL & WATER SOLENOID VALVE
OIL PRESSURE SW.
ENGINE RUN SW.
OVERSPEED SW.
ENGINE WATER TEMP. SW.
FUEL SOLENOID
BATTERY #2 INPUT(+)
BATTERY #1 CRANK
100-240VAC POWER
BATTERY #2 CRANK
FUEL INJECTOR FAIL
ECM IN ALTERNATE
BATTERIES (-)
BATTERIES (-)
ECM WARNING
HIGH RAW WATER TEMP
ECM FAILURE
LOW ENGINE TEMPERATURE
LOW RAW WATER FLOW