Magnum
1812.900A
39
Table 3-5: Undervoltage Release
Control Voltages Operational Voltage
Range 85-110%
Dropout Volts 30-
60%
Inrush/Continuous Power
Consumption
1 2
Opening Time
(ms)
24 Vdc
1
20-26 Vdc 7-14 Vdc 250 W/18 W 70
32 Vdc
1
27-35 Vdc 10-19 Vdc 275 W/15 W 70
48 Vdc
1
41-53 Vdc 14-29 Vdc 275 W/18 W 70
110-125 Vdc
1
94-138 Vdc 33-75 Vdc 450 W/10 W 70
220-250 Vdc
1
187-275 Vdc 66-150 Vdc 450 W/10 W 70
110-127 Vac
2
94-140 Vac 33-76 Vac 450 VA/10 VA 70
208-240 Vac
2
177-264 Vac 62-144 Vac 400 VA/10 VA 70
380-415 Vac
2
323-457 Vac 114-249 Vac 480 VA/10 VA 70
480 Vac
2
408-528 Vac 144-288 Vac 400 VA/10 VA 70
600 Vac
2
510-660 Vac 180-360 Vac 400 VA/10 VA 70
1
Required for 200 ms
2
Required for 400 ms
Table 3-6: Auxiliary Switch, Overcurrent Trip Switch and
Cell Switch Contact Ratings
Control Voltages Contact Rating Inductive Load
(amperes)
250 Vac 10
125 Vdc 0.5
250 Vdc 0.25
Table 3-7: Motor Operator
Control Voltages
1
Operational Voltage
Range 85-110%
Running
Current (A. avg.)
Typical Inrush Current Power Consumption
(watts or VA)
Maximum Charging
Time (seconds)
24 Vdc 20-26 12.0 300% of Running 300 5
48 Vdc 41-53 5.0 500% of Running 250 5
110-125 Vdc 94-138 2.0 600% of Running 250 5
220-250 Vdc 187-225 1.0 600% of Running 250 5
110-127 Vac 94-140 2.0 600% of Running 250 5
208-240 Vac 177-264 1.0 600% of Running 250 5
1
AC voltages are 50/60Hz