EasyManua.ls Logo

Eaton Magnum PXR - Page 17

Eaton Magnum PXR
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17
Overview of the Magnum PXR low voltage circuit breaker
MAGNUM PXR PRODUCT GUIDE PA013006EN September 2022 www.eaton.com
1
Table 1. Terminal to accessory assignment
PXR point
position
PXR point
name
General description Function Individual point description
C1 O1NO
Overcurrent trip switch 1 Indicates when breaker opens via the trip unit
Overcurrent trip switch 1 make
C2 O1C Overcurrent trip switch 1 common
C3 O1NC Overcurrent trip switch 1 break
C4 O2NO
Overcurrent trip switch 2 Indicates when breaker opens via the trip unit
Overcurrent trip switch 2 make
C5 O2C Overcurrent trip switch 2 common
C6 O2NC Overcurrent trip switch 2 break
C7 G1
External ground fault source / zero
sequence sensor
External ground fault sensor trip unit input for source /
zero sequence sensing
Ground fault sensor lead 1
C8 G2 Ground fault sensor lead 2
C9 SC Closing spring charged Closed when spring is fully charged Spring charged switch output
C10 RY1
Trip unit relays
Alarm 1 - Default setting: Maintenance mode active
(ARMS trip units) or Health warning (non-ARMS trip
units)
Configurable relay 1
C11 RY2
Alarm 2 - Default setting: Ground fault trip (LSIG trip
units) or High load alarm (LSI trip units)
Configurable relay 2
C12 RY3 Alarm 3 - Default setting: Any current protection trip Configurable relay 3
C13 RYC Relay common Configurable relay common
C14 +24V Trip unit auxiliary power supply input External trip unit power Auxilliary power supply positive
C15 0V Auxilliary power supply common
C16 N
External neutral current sensor
Connect to the external neutral current sensor, jumper if
not needed and in a 4-pole breaker
Neutral current sensor lead 2
C17 N• Neutral current sensor lead 1 (N DOT)
C18 MM Remote maintenance mode enable Enable maintenance mode via a remote switch Maintenance mode signal
C19 ZI ZSI - Input
Connect to other ZSI enabled breakers in the system
(maximum length of 25 meters (75 feet) using AWG #22
wire)
Zone selective interlock input
C20 ZC Trip Unit Circuit Common Zone selective interlock common
C21 ZO ZSI - Output Zone selective interlock output
C22 MBA
Modbus RTU Modbus RTU communication onboard trip unit
Non-Inverting (+) Signal
C23 MBB Inverting (-) Signal
C24 MBG RS485 ground
C25 a COMO Future
C26 a COMC Future
C27 a CM3
Trip unit communication adapter
module (CAM) connections
Connect to a CAM
RX+ / CMM1
C28 a CM4 RX- / CMM2
C29 a CM1 TX+ / CMM3
C30 a CM2 TX- / CMM4
C31 a Future
C32 a Future
C33 a Future
C34 a Future
C35 a Future
C36 a Future

Table of Contents

Other manuals for Eaton Magnum PXR

Related product manuals