25
Technical data and ratings
MAGNUM PXR PRODUCT GUIDE PA013006EN September 2022 www.eaton.com
2
Table 5. Magnum PXR low voltage power circuit breakers ANSI
rms Symmetrical current ratings kA 50/60 Hz
Frame
amperes
Breaker
type catalog
position 1-6 Frame type
Interrupting
rating at 254
Vac
Interupting
rating at 508
Vac
Interrupting
rating at 635
Vac
Short time
withstand
rating at
254/508 Vac
Short time
withstand
rating at
635 Vac
Poles
available
4000 MPN-640,
4N, 4A
Double narrow 65 65 65 65 65 3 & 4
MPN-840,
4N, 4A
Double narrow 85 85 65 85 65 3 & 4
MPN-C40,
4N, 4A
Double narrow 100 100 65 100 65 3 & 4
MPS-840,
4N, 4A
Double 85 85 85 85 85 3 & 4
MPS-C40,
4N, 4A
Double 100 100 100 100 100 3 & 4
5000 MPN-65N Double narrow 65 65 65 65 65 3 & 4
MPN-85N Double narrow 85 85 65 85 65 3 & 4
MPN-C5N Double narrow 100 100 65 100 65 3 & 4
MPS-850,
5N, 5A
Double 85 85 85 85 85 3 & 4
MPS-C50,
5N, 5A
Double 100 100 100 100 100 3 & 4
6000 MPS-860,
6N, 6A
Double 85 85 85 85 85 3 & 4
MPS-C60,
6N, 6A
Double 100 100 100 100 100 3 & 4
(continued)