Page 19
SK-90510-Y4_EN
ENGLISH
6. Specifications
MBP6Ki MBP11Ki MBP11Ki31
Input
Terminal blocks
Input Bypass
N/A Terminal Blocks Terminal Blocks
Output
2 IEC 16A + 3IEC 10A +
Terminal blocks
4 IEC 16A + Terminal blocks 4 IEC 16A + Terminal blocks
Overall dimensions D x W x H (inch / mm)
5.6 x 7.0 x 5.1 /
142 x 177 x 130
6.8 x 13.2 x 5.1 /
172 x 336 x 130
6.9 x 13.2 x 5.1 /
176 x 336 x 130
Weight (lb / kg)
5.5 / 2.5 12.1 / 5.5 12.1 / 5.5
Performance
Nominal voltage 200 - 240 V ~ 200 - 240 V ~ 350 - 430 V ~
Frequency 50/60 Hz
Input nominal
current
30A 50A 50A
Maximal power 6000 VA 11000 VA 11000 VA
Standards (HotSwap MBP used with UPS)
Safety IEC/EN 62040-1 / Ed.1: 2008
EMC IEC 62040-2 / Ed.2: 2005 EN 62040-2 / Ed.2: 2006
Performance IEC/EN 62040-3 / Ed.2.0: 2011.
ESD IEC 61000-4-2 : level 3.
Radiatedeld IEC 61000-4-3 : level 3.
EFT IEC 61000-4-4 : level 4.
Fast transients IEC 61000-4-5 : level 4.
Electromagnetic
eld
IEC 61000-4-6 : level 3.
Conducted
magneticeld
IEC 61000-4-8 : level 4.
Marking
CE
Environment
Operating
temperature
0 to 40°C (32 to 104°F)
Storage
temperature
-15 to 60°C (5 to 140°F)
Transit temperature -25 to 55°C (-13 to 130°F)
Humidity 0 to 95% no condensing
Operation Altitude Up to 3,000 meters (9,843 ft) above sea level with 10% derating per 1000m
Transit Altitude Up to 10,000 meters (32,808 ft) above sea level