Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117—Rev 01 15
CChhaapptteerr 55 OOppeerraattiioonn
55..11 AAcccceessss
The Mini PDU has (2) locking doors in the front of the unit:
Clear Lexan door to access circuit breaker panelboard.
Dead front door to access components and wiring.
The unit has a rear locking door to access output receptacles. Side panels lift off.
Figure 9. Mini PDU Locking Doors
Front Doors
Rear Door
Lexan Door
Dead Front Door
55..22 CCoonnttrroollss
The only controls on the unit are circuit breakers:
The Main Input Circuit Breaker turns on power to the transformer.
The Subfeed Circuit Breaker turns on power to the panelboard.
The Panelboard Circuit Breakers turn on power to the servers.
There is no Emergency Power Off (EPO) switch. The customer should provide an upstream emergency
shutdown trip function.