EasyManua.ls Logo

Eaton NFMVA20L - User Manual

Eaton NFMVA20L
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
IF 1848
Champ LED Floodlight
NFMVA20L/25L LED Fixtures
Installation & Maintenance Information
IF 1848 • 03/19 Copyright
®
2019, Eaton’s Crouse-Hinds Division Page 1
WARNING
To avoid the risk of fire, explosion or electric shock, this product should be
installed, inspected and maintained by a qualified electrician only, in accordance
with all applicable electrical codes.
WARNING
To avoid electric shock:
Be certain electrical power is OFF before and during installation and
maintenance.
Floodlight must be supplied by a wiring system suitable per local code with
an equipment grounding conductor.
To avoid burning hands:
Make sure LEDs and drivers are cool to touch when performing
maintenance.
WARNING
To avoid explosion:
Make sure the supply voltage is the same as the rated floodlight voltage.
Do not install where the marked operating temperatures exceed the
ignition temperature of the hazardous atmosphere.
Do not operate in ambient temperatures above those indicated on the
floodlight nameplate.
Use only replacement parts from Eaton’s Crouse-Hinds Division.
Use proper supply wiring as specified on the floodlight nameplate.
All surfaces must be clean.
LED compartment non-serviceable. Do not open.
Before opening wiring compartment, electrical power to the floodlight
must be turned off and area must be free from hazardous atmosphere.
Keep tightly closed when in operation.
To minimize the risk from electrostatic discharge, when cleaning, wipe the
lens with a clean, damp cloth.
INSTALLATION
Mounting
Yoke Mount - Wall Mount Using Floodlight Yoke Only
1. Using floodlight yoke as a template, mark and drill desired location on mounting
surface.
2. Secure floodlight yoke to surface using ½” bolts or lag screws (not provided).
WIRING
Wiring the Floodlight
1. Open back cover/heat sink by loosening nine (9) #10-24 x 0.75” stainless steel
cover screws using a 5/16” nut socket or flat head screwdriver
(see Figure 1).
The heat sink cover should be removed by pulling back on one corner of the top
most edge to prevent damage to gasket.
NOTE: To avoid pinching hazard between heat sink cover and driver housing, ensure
that floodlight is oriented in vertical position before, and during, wiring procedure.
2. All components in the fixture are pre-wired so only line in, neutral and ground
need to be connected in the fixture using the supplied Wago connectors, using
methods that comply with all applicable codes. See Figure 2 for wiring diagram.
Wire range from AWG 18-14 (0.75 - 2.5mm²) for neutral, and line (strip
length 0.43” [10.9mm]), and AWG 16-14 (1.5 - 2.5mm²) for ground
connections (strip length 0.43” [10.9mm]).
Entries to driver housing shall be sealed, using HTL or STL, with
devices rated a minimum of IP66.
Standard openings are M20, M25 or 3/4” NPT.
Optional openings are M20 (20mm) and/or M25 (25mm).
Secure all electrical connections and wiring entry glands.
Ensure that the following lengths for field wiring, internal to the driver
housing compartment, are followed:
– 4.5” ± 0.25” (114 ± 6mm) for ground wire
– 2.5” ± 0.25” (64 ± 6mm) for neutral wire
– 2” ± 0.25” (51 ± 6mm) for line in wire
APPLICATION
LED floodlight construction is designed for use indoors and outdoors in marine and wet
locations, where moisture, dirt, corrosion, vibration and rough usage may be present.
NFMV:
IECEx:
IEC, ATEX:
IECEx UL 15.0029X
DEMKO 15 ATEX 1377X
DEMKO 15 ATEX 1383
Ex ec IIC T4 Gc Tamb -40°C to +55°C
Ex tb IIIC T81C Db Tamb -40°C to +40°C
II 3 G Ex ec IIC T4 Gc Tamb -40°C to +55°C
II 2 D Ex tb IIIC T81C Db IP66 Tamb -40°C to +40°C
Refer to the floodlight nameplate for specific classification information, maximum
ambient temperature suitability and corresponding operating temperature (T-number).
IEC STANDARDS:
IEC 60079-0:2011+ Corr.1(2012-01) + Corr. 2 (2013-12) + I-SH 01 (2013-11) + I-SH
02 (2014-10) / EN 60079-0:2012 + A11:2013
IEC 60079-7:2017/ EN 60079-7:2015
IEC 60079-31:2013/ EN 60079-31:2014
IEC 60598-1:2008/EN60598-1:2008
IEC 60598-2:2008/EN60598-2:2008
IP66
LED floodlights are supplied for use with a choice of voltages:
• 100-277 VAC, 50/60 Hz and 127-300 VDC
• 347-440 VAC, 50/60 Hz
COVER SCREWS
LINE TERMINAL
NEUTRAL TERMINAL GROUND TERMINAL
Figure 1
Cover/heat sink
DO NOT PLACE
ADDITIONAL WEIGHT
ON THE BACK COVER/
HEAT SINK

Questions and Answers

  • S
    Summer CollinsAug 20, 2025
    What to do if the Power LED is not lit on my Eaton Industrial Electrical?
    • A
      Angela MatthewsAug 20, 2025
      If the Power LED is not lit on your Eaton Industrial Electrical, you should first check the polarity and integrity of the trunk cable connections to the enclosure. Also, verify that the d.c. supply powering the incoming trunk is operating correctly.
  • E
    Elizabeth KlineAug 22, 2025
    What to do if the power LED is not lit on my Eaton Control Unit?
    • C
      christinagarciaAug 22, 2025
      If the power LED on your Eaton Control Unit isn't lit, verify the polarity and integrity of the trunk cable connections to the enclosure. Also, check that the d.c. supply powering the incoming trunk is operating correctly.
  • N
    nstanleyAug 25, 2025
    What to do if alarms on my Eaton Security System remain on and cannot be reset?
    • L
      Lee MosleyAug 25, 2025
      If alarms are set to operate from normally closed contacts and the signal supply fuse blows, all alarms will operate as though an alarm has occurred. To resolve this, check the signal supply fuse F1 (rated at 125mA), located in the top right-hand corner of the unit when viewed from the rear, to see if it has blown. Also, ensure that the inputs have been correctly set to operate from either a normally open (N.O.) or normally closed (N.C.) configuration and haven't been accidentally inverted.
  • B
    Brittany SmithAug 26, 2025
    How to fix the audible alarms not sounding on my Eaton Security System?
    • R
      Ruth AlvarezAug 27, 2025
      Each channel can be selected to operate either of the two integral horns / horn relays as required. Internal horns and horn relays are enabled by placing the following switches to the ON position on the SPR Card: HNA – SW5 - Position 5, HNB – SW5 - Position 6. Each pair of channels can be set to activate either of the audibles using the following switches located on each alarm module: Channel 1 & 2 HNA – SW4 Position 7 set to ON, HNB – SW4 Position 8 set to ON; Channel 3 & 4 HNA – SW6 Position 7 set to ON, HNB – SW6 Position 8 set to ON.
  • J
    Jodi CarterAug 27, 2025
    What to do if signal inputs that alarm and quickly return to normal are not being picked up by the Eaton Security System annunciator?
    • U
      umunozAug 28, 2025
      Check that the response time has been set to suit the application.
  • V
    Veronica SnyderAug 30, 2025
    Why individual repeat relays do not act as slaves of the signal input on my Eaton Security System?
    • J
      James McconnellAug 30, 2025
      The operation of the repeat relays is selectable by the user to either follow the signal contact or to remain in the alarm state until the input has returned to normal and the operator has cleared the alarm.
  • A
    andregibsonAug 31, 2025
    How to troubleshoot a non-lit green LED for supply 1 and active power failure alarm on my Eaton Security System?
    • J
      Jessica MooreSep 1, 2025
      Measure the voltage on the power input terminals marked supply 1 located on the rear of the unit and verify that the level matches the requirement and is connected in the polarity indicated.
  • B
    Brandon AndersenSep 2, 2025
    How to troubleshoot a non-lit green LED for supply 2 and active power failure alarm on my Eaton Security System?
    • B
      bnelsonSep 2, 2025
      Measure the voltage on the power input terminals marked supply 2 located on the rear of the unit and verify that the level matches the requirement and is connected in the polarity indicated.
  • S
    Spencer PalmerSep 4, 2025
    What to do if no alarm occurs on the annunciator when the signal input contact closes or opens on my Eaton Security System?
    • A
      adamortizSep 4, 2025
      Check that the signal supply fuse F1 rated @ 125mA, located in the top right hand corner when viewed from the rear of the unit, is in working order and check that the corresponding signal supply voltage is present on the customer terminals on the rear of the unit which can be measured between terminals OVC and any of the terminals marked C (Common) located at the top of each row of signal input terminals.
  • E
    Erin MorganSep 6, 2025
    How to solve the Individual channel Repeat Relay contact is Normally Closed in the non alarm state but should be Normally Open on my Eaton Security System?
    • M
      madisonschneiderSep 6, 2025
      Each pair of repeat relays can be set to normally energised or normally de-energised using switches located on the Alarm Card and the contact state can also be selected as normally open or closed.

Eaton NFMVA20L Specifications

General IconGeneral
BrandEaton
ModelNFMVA20L
CategoryLighting Equipment
LanguageEnglish

Related product manuals