EasyManua.ls Logo

Eaton PDI WaveStar TFA STS 250-600A - Chapter 4 Installation TFA STS 250-600 A Models; 4.1 Placing the TFA STS 250-600 A Unit

Eaton PDI WaveStar TFA STS 250-600A
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P-164001113—Rev 01 19
CChhaapptteerr 44 IInnssttaallllaattiioonn TTFFAA SSTTSS 225500--660000AA MMooddeellss
Severe or fatal injury can result from electrical shock during contact with high voltage conductors,
monitoring PCBs, or similar equipment.
Disconnect power before drilling holes, attaching cables or conduit, or connecting STS units to other
power distribution equipment.
Use Lock Out/Tag Out procedures.
Wear suitable personal protective clothing and use protective equipment for performing mechanical and
electrical installations.
Leave ample space for attaching and routing wires.
!
IMPORTANT
A licensed electrician must install each unit.
This chapter describes installation of TFA STS 250-600A models. Installation is the responsibility of the Installer,
who must be an electrician certified for the locality where the installation is being performed.
44..11 PPllaacciinngg tthhee TTFFAA SSTTSS 225500--660000AA UUnniitt
44..11..11 PPllaacceemmeenntt IInnffoorrmmaattiioonn
TFA STS Dimensions: 50"W x 36"D x 84"H
Clearances:
Service clearance 36" front only
Ventilation clearances:
6" both sides and rear
18" top
Weight: Approx. 1400-1500 lbs. (Insure TFA STS floor loading does not exceed the raised floor loading
specifications. Obtain floor bracing if necessary.
If a floor stand is used, add floor stand weight (165-300 lbs. depending on height) to floor loading
computation: See table of floor stand weights in Figure 19.
44..11..22 MMoouunnttiinngg TTFFAA SSTTSS oonn FFlloooorr
The TFA STS is front-access-only for installation as well as maintenance, service, and operation. In constrained
spaces, the Installer may not be able to reach the rear mounting holes of the side floor brackets. Consequently,
the TFA STS comes with (2) rear-mounted floor brackets that should be installed before moving the TFA STS
into place. The following placement procedure assumes that rear access is not available.
Placement procedure:
1. Determine the position of the TFA STS precisely, including clearances.
2. Attach the (2) rear floor brackets to the floor based on your measurements and dimensions in the
illustration below. Installer chooses and provides floor attachment hardware.