9 Available protection settings
PXR TRIP UNITS FOR POWER DEFENSE MOLDED CASE CIRCUIT BREAKERS MN012007EN June 2018 www.eaton.com
Register
number
Bit
field
Mask
field
Set point
name R/W Format Value definition Unit
403004 Style1 R Encoded
0 = false
1 = true
b0 --> LdSel : with long delay protection
b1 --> SdSel : with short delay protection
b2 --> InstSel : with Inst protection
b3 --> GfSel : with ground fault protection
b4 --> ARMSel : with maintenance mode
b5 --> OvrideSel : with override protection
b6 --> RCDSel : with ground fault RCD
b7 --> MotorSel : with motor protection
b8 --> NeuSenorSel : with neutral sensor
b9 --> ThermalSel : with thermal memory
b12 --> VoltSel : with voltage sampling feature
b13 --> ExtADCSel : with external AD7779
403005 3-0 0x000F Style2 R Encoded
0 = false
1 = true
b0 --> ModbusSel : with integrated Modbus
b1 --> CAMSel : with CAM RS422 port
b2 --> IOModuleSel : with IO module port
b3 --> RelaySel : with relay
b4 --> ZSISel : with ZSI
b12 --> NZM_ACB_Sel
b13 --> IECSel : IEC = 1, UL = 0
403006 8 0x0100 Maintenance
mode: state
R Encoded 0 = Off 1 = On
0 0x0001 Maintenance
mode: remote
control
R/W Encoded 0 = Off 1 = On
403007 2-0 0x0007 Arms level R/W Encoded 1 = 2.5 * In
2 = 4 * In
3 = 6 * In
4 = 8 * In
5 = 10 * In
A
403008 Frequency R Unsigned Range: 50, 60 , 400 Hz
403009 0 0x0001 Rev feed R/W Encoded 0 = Forward 1 = Reverse
403010 0 0x0001 Sign convention R/W Encoded sign convention :
0 = IEC, 1 = IEEE, 2 = IEEEalt
403011 Power window R/W Encoded Power demand window :
0 = fixed, 1 = sliding
403012 Power interval R/W Encoded Power demand interval:
[5…60] min
min
403013 Language R/W Encoded set language on local LCD display
0x01 --> English
0x02 --> German
0x03 --> French
0x04 --> Spanish
0x05 --> Italian
0x06 --> Chinese
0x07 --> Russian
0x08 --> Dutch
0x09 --> Danish
0x10 --> Greek
0x11 --> Portuguese
0x12 --> Swedish
0x13 --> Finnish
0x14 --> Czech
0x15 --> Estonian
0x16 --> Hungarian
0x17 --> Lithuanian
0x18 --> Latvian
0x19 --> Polish
0x20 --> Slovenian
0x21 --> Slovak
0x22 --> Bulgarian
0x23 --> Romanian
0x24 --> Croatian
403014 LCD_rotation R/W Encoded Setting LCD display direction
0 <--> horizontal
1 <--> vertical - left
2 <--> vertical - right
403015 Relay_config1 R/W Encoded Relay 1/2/3 function configuration
403016 Relay_config2 R/W Encoded OFF_RELAY = 0x0000