Step 5—Standard Parameter List
PowerXL DH1 Series Variable Frequency Drives MN040039EN—April 2018 www.eaton.com 27
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Protections
P5.1.10
2
Switching Frequency MinSwitchFreq MaxSwitchFreq kHz DefaultSwitch
FreqCT
2522
P5.1.11
2
Sine Filter Enable 0 1665 See Par ID 1679
P5.1.12
1
2
OverVoltage Control 1 294 See Par ID 1679
Table 30. Basic Setting—P5.1, continued
Code Parameter Min. Max. Unit Default ID Note
Table 31. Motor—P6.1
Code Parameter Min. Max. Unit Default ID Note
P6.1.1
1
2
Output Phase Fault 2 308 0 = No Action
1 = Warning
2 = Fault
3 = Fault, Coast
P6.1.2
1
2
Ground Fault 2 309 See Par ID 308
P6.1.3
2
Ground Fault Limit 0 30 % 15 2158
P6.1.4
1
2
Motor Thermal Protection 2 310 See Par ID 308
P6.1.5
2
Motor Thermal F0 Current 0.0 150.0 % 40.0 311
P6.1.6
2
Motor Thermal Time 1 200 min 12 312
P6.1.7
1
2
Stall Protection 0 313 See Par ID 308
P6.1.8
2
Stall Current Limit 0.1 ActiveMotor
NomCurr*2
A ActiveMotorNom
Curr*13/10
314
P6.1.9
2
Stall Time Limit 1.0 120.0 s 15.0 315
P6.1.10
2
Stall Frequency Limit 1.00 See Par ID 102 Hz 25.00 316
P6.1.11
1
2
Underload Protection 0 317 See Par ID 308
P6.1.12
2
Underload Fnom Torque 10.0 150.0 % 50.0 318
P6.1.13
2
Underload F0 Torque 5.0 150.0 % 10.0 319
P6.1.14
2
Underload Time Limit 2.00 600.00 s 20.00 320
P6.1.15
1
2
Thermistor Fault Response 2 333 See Par ID 308
P6.1.16
1
2
PT100 Fault Response 2 337 See Par ID 308
P6.1.17
2
Preheat Mode 0 2159 See Par ID 1679