Step 5—Standard Parameter List
PowerXL DH1 Series Variable Frequency Drives MN040039EN—April 2018 www.eaton.com 29
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Table 32. Drive—P6.2
Code Parameter Min. Max. Unit Default ID Note
P6.2.1
2
Line Start Lockout 2 750 0 = Disabled, No Change
1 = Enable, No Change
2 = Disabled, Changed
3 = Enable, Changed
P6.2.2
2
Fault Reset Start 0 2483 0 = Start/Stop After Fault Reset
1 = Restart After Fault Reset
P6.2.3
1
2
4mA Input Fault 0 306 0 = No Action
1 = Warning
2 = Warning: Previous Freq
3 = Warning: Preset Freq
4 = Fault
5 = Fault, Coast
P6.2.4
1
2
4mA Fault Frequency 0.00 See Par ID 102 Hz 0.00 331
P6.2.5
1
2
External Fault 2 307 See Par ID 308
P6.2.6
1
2
Input Phase Fault 2 332 See Par ID 308
P6.2.7
1
2
Uvolt Fault Response 2 330 See Par ID 308
P6.2.8
1
2
Unit Under Temp Prot 2 1564 See Par ID 308
P6.2.9
1
2
RTC Fault 1 955 See Par ID 308
P6.2.10
1
2
Replace Battery Fault
Response
1 1256 See Par ID 308
P6.2.11
1
2
Replace Fan Fault Response 1 1257 See Par ID 308
P6.2.12
2
Cold Weather Mode 0 2126 See Par ID 1679
P6.2.13
2
Cold Weather Volt. Level 0.0 20.0 % 2.0 2127
P6.2.14
2
Cold Weather Time Out 0 10 min 3 2128
P6.2.15 Cold Weather Password 2129
P6.2.16 Under Temp Fault Override 2130 See Par ID 2118
P6.2.17
2
STO Fault Response 2 2427 0 = No Action
1 = Warning
2 = Fault
Table 33. Communication—P6.3
Code Parameter Min. Max. Unit Default ID Note
P6.3.1
1
2
Fieldbus Fault Response 2 334 0 = No Action
1 = Warning
2 = Fault
3 = Fault, Coast
4 = Warning, Coast
P6.3.2
1
2
OPTCard Fault Response 2 335 See Par ID 308
P6.3.3
1
2
IP Address Confliction Resp 1 1678 See Par ID 308
P6.3.4
1
2
Keypad Comm Fault
Response
2 2157 See Par ID 308