Step 5Standard Parameter List
30 PowerXL DH1 Series Variable Frequency Drives MN040039EN—April 2018 www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Table 34. Auto Restart—P6.4
Code Parameter Min. Max. Unit Default ID Note
P6.4.1
2
AR Wait Time 1.00 300.00 s 1.00 321
P6.4.2
2
AR Trail Time 0.00 600.00 s 30.00 322
P6.4.3
2
AR Start Function 0 323 0 = Flying Start
1 = Ramp
P6.4.4
2
Undervoltage Attempts 0 10 1 324
P6.4.5
2
OverVoltage Attempts 0 10 1 325
P6.4.6
2
OverCurrent Attempts 0 3 0 326
P6.4.7
2
4mA Fault Attempts 0 10 0 327
P6.4.8
2
Motor Temp Fault Attempts 0 10 0 329
P6.4.9
2
External Fault Attempts 0 10 0 328
P6.4.10
2
Underload Attempts 0 10 0 336
Table 35. Fire Mode—P9
Code Parameter Min. Max. Unit Default ID Note
P9.1
1
2
Fire Mode Function 0 535 0 = Closing Contact
1 = Opening Contact
P9.2
1
2
Fire Mode Ref Select
Function
0 536 0 = Fire Mode Min Frequency
1 = Fire Mode Ref
2 = Fieldbus Ref
3 = AI1
4 = AI2
5 = AI1 + AI2
P9.3
2
Fire Mode Min Frequency See Par ID 101 See Par ID 102 Hz 15.00 537
P9.4
2
Fire Mode Freq Ref 1 0.0 100.0 % 75.0 565
P9.5
2
Fire Mode Freq Ref 2 0.0 100.0 % 100.0 564
P9.6 Fire Mode Test Enable 2443 See Par ID 1679