Step 5Standard Parameter List
PowerXL DH1 Series Variable Frequency Drives MN040039EN—April 2018 www.eaton.com 31
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Bypass
Table 36. Basic Setting—P10.1
Code Parameter Min. Max. Unit Default ID Note
P10.1.1
12
Bypass Enable 1 1418 See Par ID 1679
P10.1.2
12
Bypass Start Delay 1 32765 s 1 544
P10.1.3
12
Auto Bypass 1 542 See Par ID 1679
P10.1.4
12
Auto Bypass Delay 0 32765 s 10 543
P10.1.5
12
OverCurrent Bypass Enable 0 547 See Par ID 1679
P10.1.6
12
IGBT Fault Bypass Enable 0 546 See Par ID 1679
P10.1.7
12
4mA Fault Bypass Enable 0 548 See Par ID 1679
P10.1.8
12
UnderVoltage Bypass
Enable
0 545 See Par ID 1679
P10.1.9
12
OverVoltage Bypass Enable 0 549 See Par ID 1679
P10.1.10
12
Motor OverTemp Bypass
Enable
0 1698 See Par ID 1679
P10.1.11
12
UnderLoad Bypass Enable 0 1699 See Par ID 1679
P10.1.12
12
External Bypass Enable 0 1700 See Par ID 1679
P10.1.13
12
Charge Switch Fault Bypass
Enable
0 1701 See Par ID 1679
P10.1.14
12
Saturation Trip Fault Bypass
Enable
0 1702 See Par ID 1679
P10.1.15
12
Under Temp Fault Bypass
Enable
0 1703 See Par ID 1679
P10.1.16
12
EEPROM Fault Bypass
Enable
0 1704 See Par ID 1679
P10.1.17
12
FRAM Fault Bypass Enable 0 1705 See Par ID 1679
P10.1.18
12
Watchdog Fault Bypass
Enable
0 1706 See Par ID 1679
P10.1.19
12
Fan Cooling Fault Bypass
Enable
0 1707 See Par ID 1679
P10.1.20
12
Keypad Com Fault Bypass
Enable
0 1708 0 = Disabled
2 = Enabled
P10.1.21
12
Option Card Fault Bypass
Enable
0 1709 See Par ID 1679
P10.1.22
12
RTC Clock Fault Bypass
Enable
0 1710 See Par ID 1679
P10.1.23
12
Ctrl Board OverTemp Fault
Bypass Enable
0 1711 See Par ID 1679
P10.1.24
12
Speed Search Start Fault
Bypass Enable
0 1712 See Par ID 1679
P10.1.25
12
Fieldbus Fault Bypass
Enable
0 1713 See Par ID 1679