Step 5—Standard Parameter List
PowerXL DH1 Series Variable Frequency Drives MN040039EN—April 2018 www.eaton.com 35
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
EtherNet Bus
P12.3.3.6 MSTP Fault Code 600 0 = None
1 = Sole Master
2 = Duplicate MAC ID
3 = Baud rate fault
P12.3.3.7
2
MSTP Fault Response 0 2526 See Par ID 2516
P12.3.3.8
1
MSTP Max Master 127 1537
Table 41. BACnet MS/TP—P12.3.3, continued
Code Parameter Min. Max. Unit Default ID Note
Table 42. Basic Setting—P12.4.1
Code Parameter Min. Max. Unit Default ID Note
P12.4.1.1
1
IP Address Mode 1 1500 0 = Static IP
1 = DHCP with AutoIP
P12.4.1.2 Active IP Address 1507
P12.4.1.3 Active Subnet Mask 1509
P12.4.1.4 Active Default Gateway 1511
P12.4.1.5 MAC Address 1513
P12.4.1.6
1
Static IP Address 192.168.1.254 1501
P12.4.1.7
1
Static Subnet Mask 255.255.255.0 1503
P12.4.1.8
1
Static Default Gateway 192.168.1.1 1505
P12.4.1.9
1
Enable BACnetIP 0 1725 See Par ID 1679
Table 43. Modbus TCP—P12.4.2
Code Parameter Min. Max. Unit Default ID Note
P12.4.2.1 Connection Limit 5 609
P12.4.2.2 Modbus TCP Unit ID 1 610
P12.4.2.3 Comm Timeout Modbus TCP 0 60000 ms 10000 611
P12.4.2.4 Modbus TCP Protocol Status 612 See Par ID 599
P12.4.2.5 Modbus TCP Fault Response 0 2517 See Par ID 2516