Step 5—Standard Parameter List
36 PowerXL DH1 Series Variable Frequency Drives MN040039EN—April 2018 www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
System
Table 44. BACnet IP—P12.4.3
Code Parameter Min. Max. Unit Default ID Note
P12.4.3.1
1
2
BACnet IP UDP port number 47808 1733 47808 = BAC0
47809 = BAC1
47810 = BAC2
47811 = BAC3
47812 = BAC4
47813 = BAC5
47814 = BAC6
47815 = BAC7
47816 = BAC8
47817 = BAC9
47818 = BACA
47819 = BACB
47820 = BACC
47821 = BACD
47822 = BACE
47823 = BACF
P12.4.3.2
2
BACnet IP Foreign Device 0 1734 See Par ID 1679
P12.4.3.3
2
BACnet IP BBMD IP 0.0.0.0 1735
P12.4.3.4
2
BACnet IP BBMD Port 47808 1737 See Par ID 1733
P12.4.3.5
2
BACnet IP Registration
Interval
0 65535 10 1738
P12.4.3.6
2
BACnet IP Comm Timeout 0 60000 0 1739
P12.4.3.7 BACnet IP Protocol Status 1740 See Par ID 599
P12.4.3.8
2
BACnet IP Fault Behavior 0 1741 See Par ID 2516
P12.4.3.9
1
BACnetIP Instance Number 0 4194302 0 1742
Table 45. Basic Setting—P13.1
Code Parameter Min. Max. Unit Default ID Note
P13.1.1 Language 0 340 0 = English
1 = ѝ᮷
2 = Deutsch
P13.1.2
1
Application 142 0 = Basic
1 = PID
2 = Advanced
P13.1.3
1
Parameter Sets 619 0 = No
1 = Reload Defaults
2 = Reload Set 1
3 = Reload Set 2
4 = Store Set 1
5 = Store Set 2
6 = Reset
7 = Reload Defaults VM
P13.1.4 Up To Keypad 620 See Par ID 2118
P13.1.5
1
Down From Keypad 621 0 = No
1 = All Parameters
2 = All, No Motor
3 = App Parameters