Table 20. Ethernet communication (Cont.).
P12.5.6
BACnet IP communication timeout
ID 1739
Minimum value:
0.00
Maximum value:
60,000
Default value:
0
Description:
Selects the time it waits before a communication fault occurs over BACnet IP.
P12.5.7
BACnet IP protocol status
ID 174 0
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Stopped;
1 = Operational; or
2 = Faulted.
Description:
This parameter shows the protocol status for BACnet IP communication.
P12.5.8
BACnet IP fault behavior
ID 1741
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Only in fieldbus control mode - when fieldbus is the control place and Fieldbus fault is active, the drive will fault on loss of
communications. If not in fieldbus control, place will not fault.
1 = In all control modes - no matter the control place setting. If communication is lost, fieldbus fault response will occur.
Description:
Defines the fieldbus fault condition for BACnet IP communication.
P12.5.9
a
BACnet IP instance number
ID 1742
Minimum value:
0.00
Maximum value:
4,194,302
Default value:
0
Description:
Displays the BACnet instance number.
P12.6 - Web UI (DM1 PRO only).
P12.6.1
Web UI protocol status
ID 2915
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Options:
0 = Off;
1 = Operational; or
2 = Faulted.
Description:
This parameter shows the protocol status for web server communication.
P12.6.2
Web UI fault response
ID 2916
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Only in fieldbus control mode - when fieldbus is the control place and fieldbus fault is active, the drive will fault on loss of
communications. If not in fieldbus control, place will not fault.
1 = In all control modes - no matter the control place setting. If communication is lost, fieldbus fault response will occur.
Description:
Defines the fieldbus fault condition for web server communication.
P12.6.3
Web UI communication timeout
ID 2919
Minimum value:
30,000 ms
Maximum value:
60,000 ms
Default value:
60,000 ms
a
Parameter value can only be changed after the drive has stopped.