15
©2015 Eaton Corporation
All rights reserved
REC Series Enclosure Installation Guide _issue 4
M6 Serrated hex flange nut
STEP 4 - SIDE PANEL EARTH BONDING
Connect the 500mm lead to the earth stud
inside the side panel as shown in FIG 5.0.
Tighten to 6Nm.
Complete STEP 4 on opposite rack side
connecting the RH side panel to the rear corner
gusset.
M6 Plain washers (X2)
M6 Serrated hex flange nut
M6 Earth lead
(350mm) - To doors
Fig 6.0
M6 Plain washers (X2)
M6 Earth lead (500mm)
Fig 5.0
STEP 5 - EARTH BONDING
TO MAIN EARTH POINTS
Taking the loose ends of the
leads fitted in STEP 3 & STEP
4, connect the leads to the
earth bonding point detailed in
STEP 1 as shown in FIG 6.0.
Tighten to 12Nm.
Repeat STEP 5 at the rear of
rack.
M6 Earth lead (350mm)
- To 19-inch rails
M6 Earth lead (500mm)
- To side panels