SV9000 Motor Pump Enhanced Protection Application Page 45 (60)
6.2.9 Group 10, Fieldbus Parameters
Fieldbus control
Fieldbus control can be activated with parameter 10.1. Then the frequency or speed reference comes
from the fieldbus as well as the Start/Stop and Reverse control.
The first two parameters in group 10 concern all fieldbuses. Parameters 10.3 - 10.6 are only for
Modbus, parameters 10.7 - 10.13 only for Profibus and 10.14 only for LonWorks.
10.1 Fieldbus control select
Defines the active control source:
0: control via I/O terminals
1: control via fieldbus board
10.2 MODBUS Slave address
0: Fieldbus control, contact open = Active control source are I/O terminals contact
closed = Active control source is the Fieldbus board
1: External Fault, closing contact = Fault is shown and motor is stopped when the input
is active
10.3 Baud rate
1: 300 baud
2: 600 baud
3: 1200 baud
4: 2400 baud
5: 4800 baud
6: 9600 baud
7: 19200 baud
10.4 Modbus Parity type
0: None
1: Even
2: Odd
10.5 Modbus time-out
The Modbus time-out determines how long the fieldbus board waits for a message from a
master device and is specified in seconds.
Time can be set between 0 - 3600 s. Time 0 s = No time-out
Parameters 10.7 to 10.13 only for Profibus DP protocol
10.6 Profibus slave address
Defines slave device address. Maximum value for this parameter is 126 and minimum 2