SV9000 Motor Pump Enhanced Protection Application Page 53 (60)
9 SV9IOC103 Control Connections
Terminal Signal Description
206 +24V Control voltage output Voltage for switches, etc. max 50 mA
207 GND I/O ground Ground for reference and controls
208 CMC Common for DIC1—DIC5 Connect to GND or +24V
209DIC1Digital Input C1
Programmable;
Default = Not Used
210DIC2Digital Input C2
Programmable;
Default = Run Enable Open Contact
211 DIC3
Acceleration/Deceleration
time selection
Contact open = time 1 selected
Contact closed = time 2 selected
212 DIC4 Jog speed selection
Contact open = no action
Contact closed = jog speed
213 DIC5 Fault Reset
Contact open = no action
Contact closed = fault reset
214 GND I/O ground
215
I
out
+ Analog output 0-20 mA/R
L
max. 500
Programmable
Default = Motor current
221 TI+
222 TI-
Thermistor Input
223 RO3/1
224 RO3/2
Relay output 3
Programmable
Default = Not used
225 RO4/1
226 RO4/2
Relay output 4
Programmable
Default = Not used
227 RO5/1
228 RO5/2
Relay output 5
Programmable
Default = Not used
Figure 9-1 Control Connections of SV9IOC103
Note! Thermistor input terminals 221 and 222 must be shorted if not used.
Signal from
Motor thermistors
1