IB131009EN
SYMPTOM
INSPECTION
REA CONTROL DEFECTS
Fails To Close
•
Closing Springs charged but
breaker does not close
•
No Closing Sound
(Close Coil does not pick up)
•
Control Power
(Fuse Blown or switch off)
•
Secondary Disconnects
•
Anti-Pump Relay
(Y relay N.C. contact open
or burned or relay picks up
•
Close Coil
(Open or Burned)
•
Latch Check Switch
(Contact open-bad switch
or trip bar not reset)
•
Auxiliary Switch
(b contact open or burned)
•
Motor Cut-off
(Contacts open or burned)
•
Trip Coil Assembly
(Clapper fails to reset)
•
Pole Shaft
(Not open fully)
•
Trip Latch Reset Spring
(Damaged or Missing)
•
Closing Sound
but no close
•
Trip Bar-D Shaft
(Fails to remain reset)
•
Trip Latch-Hatchet
(Fails to remain reset)
•
Trip Floor Tripper
(Fails to remain reset)
•
Close Latch
(Binding)
•
Close Latch Roller
(Binding)
•
Trip Circuit Energized
Undesirably Closes
•
Control Circuit
•
Close Circuit
(CS/C Getting Shorted)
•
Close Release Latch
(Fails to reset)
•
Mechanism
•
Close Floor Tripper