IB131009EN

SYMPTOM
INSPECTION
AREA
CONTROL
DEFECTS
Fails to Trip
No Trip Sound
Control Circuit
Control Power
(Fuse blown or switch off)
Secondary Disconnect
Auxiliary Switch
(a contact no making,
poor or burned)
Trip Coil
(Burned or open)
Terminals and Connections
(Poor or burned or open)
Trip Mechanism
Trip Clapper
(Jammed)
Trip Bar, Trip Latch
(Jammed)
Trip Sound
Trip Mechanism
Pole Shaft
(Jammed)
Operating Rod Assembly
(Broken or pins out)
Vacuum Interrupter
(One or more Welded)
Undesirably Trips
Control Circuit
Control Power
(SD/T Switch, remains made)
Mechanism
Trip Coil Clapper
(Not resetting)
Trip Bar or Trip Latch
(Poor engagement of mating
or worn surfaces)
Trip Bar Reset Spring
(Loss of torque)