WaveLinx User Manual
www.eaton.com/wavelinx
During the pairing process, as devices join, a message may be briefly displayed on the screen. The mobile application will also display a
device count of how many devices are paired with the Wireless Area Controller.
Pairing Device count
Device joined message
Tap on the device count to open a link that shows a paired device list organized by device type.
Scroll down to view more items within this window.
Tap to open Paired Device list
Operation of Devices within the Construction Grouping
Once construction group pairing is complete, all paired devices will operate as one large area or room.
Any wallstation in the group will operate all the paired lighting (standard ambient, industrial and outdoor integrated sensors,
tilemount sensors, wireless Dimming Switchpacks, and wireless outdoor lighting control modules) and receptacles per the default
scenes and programming.
All occupancy sensors work together. Any occupancy sensor sensing motion will turn the entire group ON (default level) and will
keep loads ON until no occupancy is detected throughout the entire area. Once occupancy ceases, after 20 minutes, controlled loads
will turn OFF.
Daylight dimming is disabled for all devices in the construction group. This includes interior and exterior devices.