20 Appendix
20.3 Technical specifications
Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-… 01/23 MN050005EN Eaton.com 179
20.3.6 CAN interfaces XC-204-…, XC-303-…
The following devices feature CAN interfaces:
a CAN interface
• XC-204-C11-003
• XC-204-C21-001
• XC-303-C11-001
• XC-303-C21-001
two CAN interfaces
• XC-303-C32-002
CAN(open) XC-204-… XC-303-…
Baud rate CAN1, CAN2 50/100/125/250/500/
1000kBits/s
50/100/125/250/500/
1000kBits/s
Device profile
to DS301V4 to DS301V4
29 Bit Identifier Yes Yes
PDO type asyn., cyc., acyc. asyn., cyc., acyc.
Connection 3 pole plug connector,
Push-In
3 pole plug connector, Push-
In
Bus termination resistors for first and last CAN
stations
120 Ω, switchable for
CAN1 with dip switch TC
120 Ω, switchable for
CAN1 with dip switch TC1
CAN2 with dip switch TC2
CANopen stations (number)
maximum 126/8 maximum 126/8
Galvanic separation from CAN1 to
Supply voltage U
Pow
Yes Yes
System bus Yes Yes
U
L
supply voltage I/Q1…I/Q4 Yes Yes
RS485
no no
CAN2
– Yes
Local inputs Yes Yes
Local outputs Yes Yes
ETH0…ETH2 Yes Yes
Galvanic separation from CAN2 to
Supply voltage U
Pow
– no
System bus – no
U
L
supply voltage I/Q1…I/Q4 – Yes
RS485
– Yes
CAN1 – Yes
Local inputs – Yes
Local outputs – Yes