20 Appendix
20.3 Technical specifications
Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-… 01/23 MN050005EN Eaton.com 179
20.3.6 CAN interfaces XC-204-…, XC-303-…
The following devices feature CAN interfaces:
a CAN interface
XC-204-C11-003
XC-204-C21-001
XC-303-C11-001
XC-303-C21-001
two CAN interfaces
XC-303-C32-002
CAN(open) XC-204-… XC-303-…
Baud rate CAN1, CAN2 50/100/125/250/500/
1000kBits/s
50/100/125/250/500/
1000kBits/s
Device profile
to DS301V4 to DS301V4
29 Bit Identifier Yes Yes
PDO type asyn., cyc., acyc. asyn., cyc., acyc.
Connection 3 pole plug connector,
Push-In
3 pole plug connector, Push-
In
Bus termination resistors for first and last CAN
stations
120 , switchable for
CAN1 with dip switch TC
120 , switchable for
CAN1 with dip switch TC1
CAN2 with dip switch TC2
CANopen stations (number)
maximum 126/8 maximum 126/8
Galvanic separation from CAN1 to
Supply voltage U
Pow
Yes Yes
System bus Yes Yes
U
L
supply voltage I/Q1…I/Q4 Yes Yes
RS485
no no
CAN2
Yes
Local inputs Yes Yes
Local outputs Yes Yes
ETH0…ETH2 Yes Yes
Galvanic separation from CAN2 to
Supply voltage U
Pow
no
System bus no
U
L
supply voltage I/Q1…I/Q4 Yes
RS485
Yes
CAN1 Yes
Local inputs Yes
Local outputs Yes

Table of Contents