Parameter Descriptions
P00: Device type selection (HM/HM+Solar/HST/HST+Solar/HCH)
P01: Gas type selection (Natural/LPG)
P03: Water filling selection (inactive/active/automatic)
P26: When the CH set temperature reaches the closing value (hysteresis off), the boiler stops
burning. Even if the temperature drops below the device opening value (hysteresis on), the boiler
does not reac-tivate until the time set by this parameter has expired. If the boiler has complaints of
frequent activation, the time in this parameter can be increased.
P35:
OTC curve selection is based on the temperature difference between the exterior temperature
and the set temperature set by the user according to the selected curve slope and the combi
boiler starts to run when it rises above that temperature difference.
P38:Hydroblock selection (Composite/Brass)
P39: Device capacity and model selection. Only V1 versions will be available.
P40: Determines the heating system type. (Radiator/floor heating)
P41: This is the parameter that determines the temperature at which the device starts to run in
ECO mode.
- Eco Mode Hysteresis ON Set Value:
- P41: The factory-set value is 1. Example: When
the CH set value is set to 30 °C, there is no flame
before the boiler return water temperature sensor
reaches 27 °C.
The value that can be set by the service is 0.
If the user wishes to consume even less fuel in
ECO mode, it can be activated by the service.
P41 1 0
Set Value CH Return Water
Temperature
CH Return Water
Temperature
30 27 22
35 27 22
40 31 26
45 34 29
50 36 31
55 40 35
60 44 39
65 47 42
70 51 46
75 53 48
80 57 52
Table 4