2
3
Eclipse Winnox WX Series v1, Installation Guide No. 111, 8/26/05
I
NT RODUCTION
This chapter is divided into two sections:
Maintenance procedures
Troubleshooting guide
Preventive maintenance is the key to a reliable, safe and
efficient system. The core of any preventive maintenance system
is a list of periodic tasks.
n
Note:
These are guidelines only. The customer should make the
final determination on maintenance intervals and tasks to
be performed while considering the working environment.
1.
Inspect the flame sensing devices for good condition and
cleanliness.
2.
Check for proper air/gas pressures (Refer to the Winnox
Data Sheets, Series 111).
3.
Test all the system alarms for proper r esponse signals.
4.
Check and clean igniter electrodes.
5.
Check the air control valv e for smooth, trouble fr e e
operation and adjustment.
6.
Check for the proper operation of ventilating equipment.
7.
Test the interlock sequence on all safety equipment.
Manually f orce each interlock to intentionally fail while at
the same time noting if related equipment closes or stops
as specified by the manufacturer. Test the flame safeguard
by manually shutting off the gas to the burner.
8.
Test the manual gas shut off cocks for proper operation.
9.
Clean and/or replace the combustion air blower filter.
10.
Inspect and clean the combustion air blower rotor.
M
AINTENANCE
Monthly Checklist
Maintenance &
Troubleshooting
5