Specification ecoGEO HP1 25-100 kW / HP3 25-100 kW
Units
HP1 25-100
HP3 25-100
Application
Place of installation
Indoors
Type of brine system
Geothermal
Heating, DHW with external storage tank and
pool
Integrated active cooling
--
Passive cooling control (External installation)
Performance
Compressor range of modulation
%
25 to 100
Heating power, B0W35
1
kW
21,1 to 86,7
COP, B0W35
1
maximum
--
4,5
Active cooling power, B35W7
1
kW
--
22,3 a 90,3
EER, B35W7
1
maximum
--
--
4,6
Maximum DHW temperature
(without external heater)
°C
60
Noise emission level
3
db
47 to 65
Energy label / ηs with average temperature
control
--
In process
Operation limits
Heating outlet temperatura range
4
°C
10 to 60 (Max setpoint 60°C)
Cooling outlet temperatura range
4
°C
-20 to 35 (Min setpoint -15°C)
Brine inlet temperature in heating mode range
4
°C
-20 to +35
Brine outlet temperature in cooling mode range
4
°C
10 to 60
Cooling circuit pressure min / max
bar
2 / 45
Heating/cooling circuit pressure
bar
0,5 to 3
Brine circuit pressure
bar
0,5 to 3
Working fluids
Refrigerant type / amout
kg
R410A/8,5
R410A/9,1
Compressor oil type / amout
kg
POE/6,7
Antifreeze fluid recommended for the source
4
-
Propylene glycol
Brine nominal flow, B0W35
1
(ΔT = 3 °C)
l/h
4765 to 19360
Production nominal flow, B0W35
1
(ΔT = 5 °C)
l/h
3625 to 14935
Electrical data:
Three phase
3/N/PE 400 V / 50 Hz
--
Maximum recommended external recomendada
5
A
C50A
Maximum consumption, B0W35
1
kW/A
20,3/31,8
Maximum consumption, B0W55
1
kW/A
29,6/45,1
Starting current min/max
6
A
10,8/16,7
Correction of cosine φ
--
0,96-1
Dimensions
and weight
Height x width x depth
mm
1000x950x900
Empty weight (without assembly)
kg
350
355
1. In compliance with EN 14511, this includes the consumption of the circulation pumps and the compressor driver.
2. Considering support provided by the emergency electrical.
3. In compliance with EN 12102, this includes the acoustic insulation kit of the compressor.
4. With variable speed circulating pumps, managed by the ecoGEO HP heat pump.
5. Maximum consumption can vary significantly according to working conditions, or if the compressor's range of operation is
restricted. Refer to the technical service manual for more detailed information.
6. Starting current depends on working condition of the hydraulic circuits.