EasyManua.ls Logo

EcoSpring ES300+ - Error Codes & Fault Resolution

Default Icon
22 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ES300 Installation & Owner’s Manual
20
19
Installation & Owner's Manual
Fault
Possible reason solution
Cold water
out and
display screen
extinguished
No hot water
Water leakage
Hydraulic pipeline joints
are not sealed well.
Bad connection between power supply plug
and socket;
Setting water temperature too low;
Temper sensor broken ;
PCB broken ;
Compressor broken .
Plug in;
Setting water temp. higher;
Contact service center.
Waiting for publi c water supply to recover;
Waiting for inlet water pressure to increase;
Open water inlet valve.
Check and reseal all joints.
Public water supply ceased;
Cold water inlet pressure too low (<0.15 MPa);
Cold water inlet valve closed.
Malfunction Description Corrective action Display
Error of sensor T5U(upper water temperature sensor) E0
Maybe the connection between sensor and PCB is broken
or sen sor has been broken.
Contact
to service the unit.
Error of sensor T5L(lower water temperature sensor) E1
Maybe the connection between sensor and PCB is broken
or sensor has been broken.
Contact
to service the unit.
Tank and Wired Controller communication error E2
Maybe the connection between controller and PCB is broken
or PCB has been broken.
Evaporator temperature sensor T3 error E4
Maybe the connection between sensor and PCB is broken
or sensor has been broken.
Contact
to service the unit.
Ambient temperature sensor T4 error E 5
Maybe the connection between sensor and PCB is broken
or sensor has been broken.
Contact
to service the unit.
Compressor discharge temperature sensor TP error E6
Maybe the connection between sensor and PCB is broken
or sensor has been broken.
Contact
to service the unit.
E8
Electric leakage error
If PCB current_induction_circuit check the current
, system consider it as
"electric leakage error"
Maybe some wires have been broken or bad wire
connection.
Contact
to service the unit.
Compressor suction temperature sensor TH error E9
Maybe the connection between sensor and PCB is broken
or sensor has been broken.
Contact
to service the unit.
EE
E-heater open-circuit error( IEH(Current
E-heater on & E-heater o )<1A)
Maybe the E-heater has been broken or bad wire
connection after repair.
Clock chip error EF
Maybe the chip has been broken, but unit can work well
without clock-menmory, so it is needed to reset clock
when power put on again.
If necessary, contact a qua
to service the
unit.
E-EPROM chip error Contact a qu on to service the unit.
Ed
P1
System high pressure protection
3.0MPa a ctive
2.4MPa inactive
System blocked, air or water or more refrigerant
in system(after repair), water temperature
sensor malfunction, e tc.
Contact a qu
on to service the unit.
9.4 Trouble Shooting
9.5 Error Code Table
Display
Malfunction Description Corrective action
E0 Error of sensor T5U(upper water temperature sensor)
Maybe the connection between sensor and PCB is broken
or sensor has been broken.
Contact a qualied person to service the unit.
E1 Error of sensor T5L(lower water temperature sensor)
Maybe the connection between sensor and PCB is broken
or sensor has been broken.
Contact a qualied person to service the unit.
E2 Tank and Wired Controller communication error
Maybe the connection between controller and PCB is broken
or PCB has been broken.
E4 Evaporator temperature sensor T3 error
Maybe the connection between sensor and PCB is broken
or sensor has been broken.
Contact a qualied person to service the unit.
E5 Ambient temperature sensor T4 error
Maybe the connection between sensor and PCB is broken
or sensor has been broken.
Contact a qualied person to service the unit.
E6 Compressor discharge temperature sensor TP error
Maybe the connection between sensor and PCB is broken
or sensor has been broken.
Contact a qualied person to service the unit.
E7 Heat pump system error
Maybe the connection between sensor and PCB is broken or sensor has
been broken. Contact a qualied person to service the unit.
E8
Electric leakage error
If PCB current_induction_circuit check the current dierence
between L,N> 14mA, system consider it as
electric leakage error
Maybe some wires have been broken or bad wire
connection.
Contact a qualied person to service the unit.
E9 Compressor suction temperature sensor TH error
Maybe the connection between sensor and PCB is broken
or sensor has been broken.
Contact to service the unit.
EE
E-heater open-circuit error( IEH(Current dierence
E-heater on & E-heater o )<1A)
Maybe the E-heater has been broken or bad wire
connection after repair.
EF Clock chip error
Maybe the chip has been broken, but unit can work well
without clock-menmory, so it is needed to reset clock
when power put on again.
If necessary, contact a qualied to service the unit.
Ed E-EPROM chip error Contact a qualied person to service the unit.
P1
System high pressure protection
3.0MPa a ctive ; 2.4MPa inactive
System blocked, air or water or more refrigerant
in system(after repair), water temperature
sensor malfunction, etc.
Contact a qualied person on to service the unit.

Other manuals for EcoSpring ES300+