Chapter 3: Programming the unit
LaserSense HSSD-2 Aspirating Smoke Detector Installers Handbook 43
Table 3: Menu reference table
Menu Submenu Programmable function Page
Setup Menu Time and Date Time HH:MM 45
Date DD:MM:YYYY
Alarm Levels Fire 2 level (1-25) 45
Fire 1 level (8-10)
Pre-Alarm level (3-8)
Aux level (2-10)
Fire 2 delay (0-90) 45
Fire 1 delay (0-90)
Pre-Alarm delay (0-90)
Aux delay (0-90)
Class. override (0-199) 45
Alarm factor (0-17) 45
Day start (0-23) 46
Night start (0-23)
LDD enable (Yes/No) 46
FastLearn On (Yes/No) 47
Auto FastLearn (Yes/No) 47
Alarm Actions Delay override (Yes/No) 47
Cascading alarms (Yes/No) 47
Latching alarms (Yes/No) 48
Latching faults (Yes/No) 48
Remote day/night (Yes/No) 48
Remote reset (Yes/No) 48
Remote isolate (Yes/No) 48
Prog. Isolate On (Yes/No) 48
Detector Detector address 48
Device text 49
Reference Reference enable (Yes/No) 49
Reference device (1-127) 49
Level (0-99) 49
Back off (0-99) 49
Front Panel ISOLATE enable (Yes/No) 49
TEST enable (Yes/No) 49
RESET enable (Yes/No) 49
Setup Menu Power Checks Power save (Yes/No) 49
Battery check enable (Yes/No) 50