(1)  Signal polarity is shown when the circuit is in supervisory state. 
Polarity reverses when the circuit is active. 
(2)  Supervised. 
(3)  Power-limited unless connected to a nonpower-limited source. If 
the source is nonpower-limited, eliminate the power-limited mark 
and maintain a minimum of 0.25 in. (6.4 mm) space from power-
limited wiring. For other mounting methods, see enclosure and 
bracket installation sheets to maintain separation of power-
limited and nonpower-limited wiring. The wire size must be 
capable of handling fault current from nonpower-limited source. 
  — or — 
  Use type FPL, FPLR, FPLP, or permitted substitute cables, 
provided these power-limited cable conductors extending beyond 
the jacket are separated by a minimum of 0.25 in. (6.4 mm) 
space or by a nonconductive sleeve or nonconductive barrier 
from all other conductors. Refer to the NFPA 70 National 
Electrical Code for more details.  
 
(4)  If using a G1-P Genesis series horn while connected to a 
compatible fire alarm control panel, a CDR-3 Bell Coder must 
be used to comply with NFPA 72 standard alarm evacuation 
signal. 
(5)  47 kΩ EOLR (P/N EOL-47). 
(6)  Signaling line circuit (SLC) to next device. 
(7)  Channel 1 (ALERT) AUX riser to next module or riser 
supervisory device. 
(8)  Power-limited regulated, power supply UL/ULC Listed for fire 
protective signaling systems. 
(9)  Channel 1 (ALERT) AUX riser from previous device. 
(10)  Signaling line circuit (SLC) from previous device. Supervised 
and power-limited. 
(11)  Channel 2 (EVAC) AUX riser from previous device. 
(12)  Channel 2 (EVAC) AUX riser to next module or riser 
supervisory device.