EasyManua.ls Logo

Edwards SIGA-CC2 - User Manual

Edwards SIGA-CC2
5 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
© 2017 United Technologies Corporation 1 / 5 P/N 387040P-EN • REV 013 • ISS 20SEP17
SIGA-CC2 Dual Input Signal Module
Installation Sheet
Description
The SIGA-CC2 Dual Input Signal Module is an addressable
device that connects one of two risers to a Class B supervised
output circuit.
When activated, the module connects the output circuit to the
Riser 1 or Riser 2 input. The input can be either 24 VDC (to
operate polarized audible and visible signal notification
appliances), or 25 or 70 VRMS (to operate audio evacuation
speakers). Typically, the Riser 1 input connects to the ALERT
channel and the Riser 2 input connects to the EVAC channel.
The module does not provide signal synchronization. To meet
UL 864 requirements for horn and strobe signal
synchronization, you must install a Genesis Signal Master
module. This module does not provide supervision of the riser;
the fire alarm panel provides this function.
The SIGA-CC2 module requires two addresses on the
signaling line circuit (SLC). Addresses are assigned
electronically. There are no address switches.
Diagnostic LEDs provide visible indication of the state of the
module through the cover plate:
Normal: Green LED flashes
Alarm/active: Red LED flashes
Personality codes
Use the personality codes described below to configure the
SIGA-CC2 module. See Table 1 for listing information.
Table 1: Personality codes
Code
Description
UL 864
CAN/ULC-
S527
EN 54-18
7
Riser selector -
supervised output
(Class B)
Personality code 7: Riser selector - supervised output
(Class B). Configures the SIGA-CC2 module as a
one - or two - input, signal power (24 VDC) or audio evacuation
(25 or 70 VRMS) riser selector. The output circuit is monitored
for open or shorted wiring. If a short exists, the control panel
inhibits the activation of the signal circuit, so the riser is not
connected to the wiring fault.
Installation
Install this device in accordance with applicable national and
local codes, ordinances, and regulations.
Notes
The module is shipped from the factory as an assembled
unit; it contains no user-serviceable parts and should not
be disassembled.
This module does not operate without electrical power. As
fires frequently cause power interruption, discuss further
safeguards with the local fire protection specialist.
To install the module:
1. Write the address assigned to the module on the label
provided, and then apply the label to the module. Remove
the serial number label from the module, and then attach it
to the project documentation.
2. Wire in accordance with Wiringon page 2.
3. Using the self-tapping screw provided, attach the wall
plate to the module. See Figure 1.
4. Using the four machine screws, attach the wall plate and
module to the electrical box.
Question and Answer IconNeed help?

Do you have a question about the Edwards SIGA-CC2 and is the answer not in the manual?

Summary

Description

Personality Codes

Installation

Protection from Transient Spikes

Wiring

General Wiring Notes

General notes for wiring the device according to applicable codes and regulations.

Riser Wiring Notes

Notes specific to riser wiring, including line impedance and survivability requirements.

Specifications

Regulatory Information

Contact Information

Summary

Description

Personality Codes

Installation

Protection from Transient Spikes

Wiring

General Wiring Notes

General notes for wiring the device according to applicable codes and regulations.

Riser Wiring Notes

Notes specific to riser wiring, including line impedance and survivability requirements.

Specifications

Regulatory Information

Contact Information

Overview

The SIGA-CC2 Dual Input Signal Module is an addressable device designed to connect one of two risers to a Class B supervised output circuit within a fire alarm system. This module acts as a selector, allowing the output circuit to be connected to either Riser 1 or Riser 2 when activated. Typically, Riser 1 is designated for the ALERT channel, while Riser 2 is used for the EVAC (evacuation) channel.

The module's primary function is to provide a supervised output for various notification appliances. When activated, it connects the output circuit to the selected riser, which can supply either 24 VDC for polarized audible and visible signal notification appliances (such as horns and strobes) or 25/70 VRMS for audio evacuation speakers. This versatility makes it suitable for a range of fire alarm system configurations.

A key feature of the SIGA-CC2 is its supervision of the output circuit for open or shorted wiring. If a short circuit is detected, the control panel will inhibit the activation of the signal circuit, preventing the riser from being connected to the wiring fault. This enhances system reliability and safety by preventing potential damage or false alarms due to wiring issues.

It's important to note that the SIGA-CC2 module itself does not provide signal synchronization. For installations requiring horn and strobe signal synchronization to meet UL 864 requirements, a separate Genesis Signal Master module must be installed. Additionally, while the module supervises its output circuit, it does not supervise the riser; this function is handled by the fire alarm control panel.

The SIGA-CC2 module requires two addresses on the signaling line circuit (SLC). These addresses are assigned electronically, eliminating the need for manual address switches. This simplifies installation and configuration.

For installations where the output circuit connects to electromechanical bells or horns, a bipolar transient protector (P/N 235196P) is recommended. This protector safeguards the module from transient spikes that can be caused by switching inductive loads. To ensure optimal protection, bells and horns should be located at least 6 ft. (1.8 m) from the module.

The module is configured using personality codes. Personality code 7, "Riser selector - supervised output (Class B)," configures the SIGA-CC2 as a one- or two-input signal power (24 VDC) or audio evacuation (25 or 70 VRMS) riser selector with a supervised output. This code ensures the module operates as intended for its specified applications.

For maintenance and diagnostic purposes, the SIGA-CC2 module includes diagnostic LEDs that provide visible indications of its state through the cover plate. A green LED flash indicates a normal state, while a red LED flash signifies an alarm or active state. These visual cues allow for quick and easy status checks, aiding in troubleshooting and system monitoring.

Installation of the SIGA-CC2 module should always be performed in accordance with applicable national and local codes, ordinances, and regulations. The module is shipped as an assembled unit and contains no user-serviceable parts, so it should not be disassembled. It requires electrical power to operate, and given that fires can cause power interruptions, additional safeguards should be discussed with a local fire protection specialist.

Wiring instructions emphasize the importance of verifying that all field wiring is free of opens, shorts, and ground faults before connection. Wires should be stripped to 1/4 inch (about 6 mm) from the ends to ensure proper connection and prevent ground faults. Each terminal on the module is limited to a single conductor. Test resistors are supplied with the SIGA-CC2 to prevent trouble signals on unused circuits during installation; these should be removed and a UL/ULC Listed 47 kΩ EOLR installed at the end of the circuit when connecting field wires. The module does not support conventional smoke detectors.

For riser wiring, it's crucial to refer to the installation manual for the specific fire alarm panel to determine maximum line impedance and ensure circuit capacitance does not exceed 0.1 µF. If the riser serves more than one notification zone, installation must comply with NFPA 72 National Fire Alarm and Signaling Code requirements for survivability from fire.

The SIGA-CC2 module is a robust and essential component for managing notification and evacuation signals in addressable fire alarm systems, offering supervised output and flexible riser selection capabilities.

Edwards SIGA-CC2 Specifications

Power IconPower
operating voltage range15.20 to 19.95 VDC
standby current310 µA
activated current135 µA
ground fault impedance10 kΩ
output rating (24 VDC)2 A
output rating (25 VRMS audio)50 W
output rating (70 VRMS audio)35 W
circuit capacitance0.1 µF max.
Operating Environment IconOperating Environment
operating temperature32 to 120°F (0 to 49°C)
relative humidity0 to 93%, noncondensing
storage temperature range−4 to 140°F (−20 to 60°C)
Weight and Dimensions IconWeight and Dimensions
electrical box minimum size3.5 × 3.5 × 1.5 in. (85 × 85 × 38 mm)
compatible electrical box depth2-1/2 in. (64 mm)
compatible electrical box depth with dual-gang cover1-1/2 in. (38 mm)

Related product manuals