On a Sloping Ceiling
With a sloping or peaked ceiling install a Smoke Alarm within 600mm of the peak or
a Heat Alarm within 150mm of the peak (measured vertically). If this height is less
than 600mm for Smoke Alarms or 150mm for Heat Alarms the ceiling is regarded
as being flat
(see Figure 4).
Locations to avoid
DON’T place Smoke Alarms in any of the following areas:
%DWKURRPV NLWFKHQVVKRZHU URRPVJDUDJHVRU RWKHUURRPV ZKHUH WKHVPRNH
alarm may be triggered by steam, condensation, normal smoke or fumes. Keep
at least 6 metres away from sources of normal smoke/fumes.
/RFDWHDZD\IURPYHU\GXVW\RUGLUW\DUHDVDVGXVWEXLOGXSLQWKHFKDPEHUFDQLPSDLU
performance. It can also block the insect screen mesh and prevent smoke from
entering the smoke detector chamber.
DEAD AIR
RFA
E
NEVER WITHIN
.
M
F ANY
RNER
IDEAL IN
ENTRE
F
EILIN
M
KE ALARM
m
HEAT ALARM
15
m
Figure 3
Figure 4
11