Construction
Data Plate
Operating principle
Symbols used on the data plate
1 Brand
2
Country of origin
3 Boiler model - Serial number
4 Commercial reference
5 Cercaon number
6
Desnaon country
- Gas category
7 Gas seng
8 Installaon type
9 Electrical data
10 Factory sengs
11 Maximum water pressure
12 Boiler type
13 NOx class / Eciency
14 Input rang nominal heang
15 Power output heang
16 Gases which may be used
17 Ambient operang temp.
18 Max. central heang temp.
26-05-2015
S/N 0000000KE000000000000
00
100% min.
ηη
= =
MAX MIN
Q(Hi)
P
P
60/80C
30/50C
gas
mbar
gas
mbar
gas
mbar
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Operating principle
The TRIGON XXL is a fully modulating
boiler.
The control unit of the boiler adapts the
modulation ratio automatically to the
heat demand requested by the system.
This is done by controlling the speed of
the fan. As a result, the mixing system
will adapt the gas ratio to the chosen
fan speed, in order to maintain the
best possible combustion gures and
therewith the best efciency.
The ue gases created by the
combustion are transported downwards
through the boiler and leave at the back
side into the ue system.
The return water from the system enters
the boiler in the lower section, where is
the lowest ue gas temperature in the
boiler.
In this section condensation takes place.
The water is being transported upwards
through the boiler, leaving the boiler at
the top (burner) section.
The cross ow working principle (water
up, ue gas down) ensures the most
efcient combustion results.
The LMS14 control unit can control the
boiler operation based on:
• xed ow temperature (stand alone
operation);
• weather compensated operation
(with optional outdoor sensor);
• 0-10V external inuence
(temperature or capacity) from a
building management system.