EasyManua.ls Logo

Elentek EXPRESS PRO - Page 20

Default Icon
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20
EMPYTING OR FILLING ANALOG SIGNAL
Visible if "PRESSURIZATION" is not activated.
This parameter allows the operating logic of the analogue signal to be
selected if "none", "cm", "m" have been selected as unit of measurement.
In FILLING mode, the motors will be enabled when the analogue signal
decreases compared to set point value (set point higher than start
threshold).
In EMPTYING mode, the motors will be enabled when the analogue signal
increases compared to set point value (set point lower than start
threshold).
FILLING
EMPTYING
ANALOG SIGNAL FULL SCALE
Visible if "PRESSURIZATION" is not activated.
This parameter allows the full scale value of the analog sensor used to be
selected.
0.0 - 999.9
SET POINT
Visible if "PRESSURIZATION" is not activated.
This parameter allows the set point to be maintained on the system to
be set.
The maximum settable value depends on the "ANALOG SIGNAL FULL
SCALE VALUE" set in the previous parameter.
0.0 - 999.9
START THRESHOLD M1 M4
Visible if "PRESSURIZATION" is not activated.
This parameter allows the first motor restart value to be set as the analog
signal decreases.
0.0 - 999.9
ALARM LEVEL THRESHOLD
Visible if "PRESSURIZATION" is not activated.
This parameter allows the alarm value to be set as the analog signal
increases.
0.0 - 999.9