ID 985/S/E/CK - ID985/E LX 7/14
PAR. DESCRIPTION
RANGE DEFAULT VALUE* LEVEL** U.M.
dPO Determines when instrument starts up if the
defrosting cycle must be activated (if the tempera-
ture on the evaporator allows this)
y=defrosting activated at start-up
n=defrosting not activated at start-up
n/y n 1-2 flag
tcd Minimum time for each compressor state before
defrosting “Ontime if >0; “Offtime if >0
-31...31 0 2 min
Cod Compressor “Off” time before defrost cycle. The
compressor is not turned on if a defrost cycle is
expected in the time indicated by the parameter.
0=Function excluded
0...60 0 2 min
Fan controller-FAn label
Defrosting controller-deF label
FPt Determines if “FSt” and “Fot” are expressed as
absolute values or in relation to set point
0=absolute value; 1=value related to set point
0/1 0 2 flag
FSt Fan stop temperature. Temperature limit that, if
exceeded by the value read by the evaporator
probe, stops the fans.
-50.0...150.0 2.0 1-2 °C/°F
Fot Fan start temperature. If the temperature read by
the evaporator probe is lower than the set value
the fans remain off.
-50.0...150.0 -50.0 2 °C/°F
NOTE: At level 1 the folders will only display all the level 1 parameters. At level 2 the folders will only display all the
level 2 parameters. The level marked 1-2 allows the parameter to be displayed at both levels.
FAd Fan activation intervention differential.
(see “FSt”, “Fot”)
1.0...50.0 2.0 1-2 °C/°F
Fdt Delay before fan activation after defrosting
0...250 0 1-2 min
dt Dripping time
0...250 0 1-2 min
FCO Disables fans with compressor off
(Off)
y = fans active (with thermostat; in response to
value read by defrost probe, see “FSt” parameter);
n = fans off;
dc = duty cycle (using parameters “Fon” and “FoF”
n/y/dc y 1-2 flag
dFd Disables evaporator fans.
y=fans disabled
n=fans enabled
y/n y 1-2 flag
Fod Enables fan stop with door open and fan re-start
when door is closed (if fans were on).
n=fans stop;
y=fans unchanged
n/y n 2 flag
FdC Fan shut-down delay after compressor stop
0=function excluded
0...99 0 2 min
Fon Fan start-up time in Duty mode
Cycle; valid for FCO=dc
0...99 0 2 min
FoF Fan shut-down time in Duty
Cycle; valid for FCO=dc
0...99 0 2 min
“dd (2) dE1...dE8; daily defrost start time
0...23/0...59 24 1 hours/min
“Fd (2) F1...F8 festive defrost start time
0...23/0...59 24 1 hours/min
(3)
SCF Condenser fan set point
-50.0...150.0 10 2 °C/°F
dCF Condenser fan differential
-30...30 2 2 °C/°F
tCF Condenser fan start-up delay after defrost
0...59 0 2 min
dCd exclusion of condenser fans in defrost mode
n/y y 2 Flag