11/14
NOTE: At level 1 the folders will only display all the level 1 parameters. At level 2 the folders will only display all the
level 2 parameters.
IWP 760 LX Fan Condenser
PAR. DESCRIPTION
RANGE DEFAULT LEVEL**
U.M.
Configuration- CnF label
H31 UP button configurability
0=disabled 1=defrosting
2=auxiliary 3=reduced set point
4=not used 5=not used
6=light 7=stand-by
8= maintenance request 9=evaporator fan ON
10=enables/disabled 11= enables/disables relay
Frame Heater relay nAd functions
H32 DOWN button configurability
(Same as H31)
0...11
0
2
num
H33 ESC button configurability
(Same as H31)
0...11
0
2
num
H34 Fnc 1 button configurability
(Same as H31)
0...11
6
2
num
H35 Fnc 2 button configurability
(Same as H31)
0...11
7
2
num
H41 Presence of control probe
n=not present y=present
n/y
y
2
flag
H42 Presence of evaporator probe
n=not present y=present
n/y
y
2
flag
H43 Probe 3 configurability:
y=probe present n=probe not present
2EP=probe on 2nd evaporator
3-1=control enabled on probe1 and/or (probe3-probe1)
n/y/2EP/3-1
n
2
flag
H44 Set point on temperature delta. Is used to set tem-
perature Delta T value (probe3-probe1), if relative
function is enabled with parameter H43=3-1
-50.0...50.0
1
2
°C/°F
H48 RTC Presence
n=not present y=present (Real Time Clock)
n/y
n
2
flag
H60 Vector number. Configures the machine for special
configuration for operating in a specific installa-
tion.
1...6
1
2
num
rEL Device version. Read only parameter
/
/
1
/
tAb Parameter table. Reserved. Read only parameters
/
1
/
Pressure switch
PrE label
PEn Number of errors allowed per minimum/maximum
pressure switch input
10
1
num
PEI Minimum/maximum pressure switch error count
time MINIMUM AND MAXIMUM TEMPERATURE
1...99
60
1
min
Frame Heater
FrH label
HOn Output ON time
0...255
5
2
ore/min/sec
HOf Output OFF time
0...255
10
2
ore/min/sec
dt3 Frame Heater controller time units of measure-
ment
0=hours: 1=minutes; 2=seconds
0/1/2
0
2
num
Copy Card
Fpr label
UL Transfer of parameter map from instrument to
Copy Card
dL Transfer of parameter map from Copy Card to
instrument
Fr (10) Formatting. Cancels all data in the Copy Card
/
/
1
/
/
/
1
/
/
/
1
/
/
0...15
H22 Digital output 2 configurability
(Same as H21)
0...12
2
2
num
H23 Digital output 3 configurability
(Same as H21)
0...12
3
2
num
H24 Digital output 4 configurability
(Same as H21)
0...12
6
2
num
H25 Digital output 5 configurability
(Same as H21)
0...12
7
2
num
H26 Digital output 6 configurability
(Same as H21)
0...12
12
2
num
0
2
0
2
6
2
7
2
y
2
y
1
y
1
0
2
-
-
-
-
/
1
/
1
15
1
99
1
1
2
6
2
0
2
/
1
/
1
/
1
2
2
3
2
7
2
0
2
0
2
CUSTOM SETTINGS
DEFAULT - LEVEL
0...11
1
2
num
1
2