Operating & Maintenance Instructions 43
FIELD NAME
OBIS Code Description
Error Flags
97.97.0
Error flags:
Bit 7-6: Reserved
Bit 5 ROM checksum error; 1 = error
Bit 4 Table 1 checksum error; 1 = error
Bit 3: Table 0 checksum error; 1 = error
Bit 2: Billing data checksum error; 1 =
error
Bit 1 Not used
Bit 0: I2c bus error; 1 = error
Rate1 Time
96.8.1
Total time in service in Rate 1, in hours (0-
99999). Incremented once an hour for each
hour the meter is in this rate
Eg. “999999” Hrs
Rate2 Time
96.8.2
Total time in service in Rate 2, in hours (0-
99999). Incremented once an hour for each
hour the meter is in this rate
Eg. “999999” Hrs
Power fail Count
96.7.0
Power fail counter. Indicates the number of
power fails. Rolls over to 1 from maximum
value of 65535. Incremented on power-up
Eg. “065535”
Watchdog Count
96.52.0
Total number of watchdog timer resets.
Does not roll over upon reaching its
maximum value of 255.
Eg. “000255”
Reverse Warning
Count
96.53.0
Reverse energy event count. Indicates the
number of separate incidents when reverse
energy was detected. Rolls over to 1 from
maximum count of 255
Eg. “000255”
Phase Fail Count
96.54.0
Indicates the number of phase failure
incidents. Rolls over to 1 from maximum
count of 65535
Eg. “065535”