EasyManuals Logo

Eltek Valere Minipack User Manual

Eltek Valere Minipack
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #37 background imageLoading...
Page #37 background image
Rev.Draw. No.Page
Format
Schematic Diagram Minipack
4 Module System -48Vdc or -60Vdc
Consultant
Replace for Replaced by
Copyright A/S Eltek. All rights reserved
Eltek
2023227
25-10-07
CHLAGB
CR 071024NB3
Sym. Date/SignAlteration
A3
ProjectionScale
Approved
FRNONO
Draw
ORSKNO
Design
ORSKNO
Date
07 Dec. 2006
31 of 1
--
-
Y X
LVBD
-FB1
-FBn
Battery Strings
Circuits -48Vdc
0r -60Vdc
0V
Customer
connections
Customer
connections
Load circuits -48Vdc
or -60Vdc
DC Earth (TE)
Customer connections
1: Optional 9 pin D-sub RS232 connection.
Can be mounted in front or on rear side of
Smartpack. Replaces ”Ext. Battery Connections”
when mounted on the rear side of Smartpack
2: Optional Web/SNMP (ENET) connection.
Replaces ”Ext. Alarm I/O Connections”
Customer
connections
CON5
System Connections
CON4
Battery connections
CON2
Ext. Alarm I/O Connections
2: Optional: Web/SNMP (ENET)
CON1
Alarm I/O Connections
USB 2.0 type B port
(PC connection)
9
1: Optional: RS232
Smartpack
monitoring and
control unit
10
CAN port
15
15
9/15
CON3
Ext. Battery connections
1: Optional: RS 232
8/26
CAN port
USB
Rear connections Front connections
8
8
See Std. Documentation
356804.10x
See Std. Documentation
356804.10x
NA for Smartpack Web/SNMP
NA for Smartpack RS232 rear
COM
NO
NC
1
Alarm Outputs and
Digital Inputs
10
2
3
4
5
6
7
8
9
10
+
-
+
-
Digital Input 1
Digital Input 2
Relay 1
COM
NO
NC
Relay 2
Con 1A*
Alarm I/O
Connections
X1*
Alarm I/O Connections
26
Digital Input 3
Digital Input 4
Digital Input 5
Digital Input 6
X2A*
Ext. Alarm I/O Connections
X2B*
Ext. Alarm I/O Connections
Customer
connections
Mains input
terminals
* To be labeled
8
L1
N
L2
N
L3
N
PE
PE
15
Alarm Outputs and
Digital Inputs
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
+
-
+
-
+
-
+
-
COM
NO
NC
Relay 3
COM
NO
NC
Relay 4
COM
NO
NC
Relay 5
COM
NO
NC
Relay 6
Con 2A*
Ext. Alarm I/O
Connections
Dist.Board 2 MPBB 100A
10pos G1
X6B*
DC output -
Y5 low pri load
Y4
Y3 Fuse
alarm
Y2 high
pri load
Y1
F1
F2
F3
F4
F5
F6
F7
F8
F9
F10
Y6
Y7
Y24
Y25
10
9
8
7
6
5
4
3
2
1
Dist board 1 Minipack System MCB
10 pos load
4 pos batt
Con5A*
Smartpack Connection
213213
JP1 JP2
NEG. DIST.
POS. DIST.
NEG. DIST.
POS. DIST.
1
2
3
4
Batt. Fuse Fail +
Batt. Fuse Fail -
LVD 1A
LVD Common
TB1
System connections
3
4
5
6
X6A*
DC output +
7
8
9
10
SH1
Y1 Power input +
Y2 Power input -
Y7
Y6
Y5
Y4
Y3
Y9
To battery contactor
To Dist
board 2
Optional
Y X
LVLD
K1
Y12
Y18
Y19
Y20
X7A*
To battery +
1
2
pin 1-8
8
7
6
5
4
3
2
1
Underwiring MPBB 6pos 3AC
X5*
Power
output + Y7
Power
output – Y8
Power module 1
PE
N
L
+
-
Power module 2
PE
N
L
+
-
Power module 3
PE
N
L
+
-
Power module 4
PE
N
L
+
-
CAN1
Smartpack
Power -/CAN bus
Interconnections
1
2
3
4
5
6
7
8
9
10
*X4
Battery Connections
Con 4A*
Battery Connections
Battery Connections
15
SERIAL
DIFF
S1
+
-
Batt. Symmetry 1
+
-
Batt. Symmetry 2
+
-
Batt. Symmetry 3
+
-
Batt. Symmetry 4
+
-
Temperature Sense 1
12
13
14
+
-
+
-
11
Not Connected
Not Connected
15
*Con 6
Temp sense
15
1
2
3
4
5
6
7
8
9
10
*X3
Battery Connections
Con 3A*
Battery Connections
Battery Connections
SERIAL
DIFF
S1
+
-
Batt. Symmetry 5
+
-
Batt. Symmetry 6
+
-
Batt. Symmetry 7
+
-
Batt. Symmetry 8
+
-
Temperature Sense 2
12
13
14
+
-
+
-
11
Battery Current 2
Battery Fuse Fail 2
15
*Con 7
Temp sense