EasyManuals Logo

Eltek Valere Minipack User Manual

Eltek Valere Minipack
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
Quick Start Guide Minipack PS System 356808.103, 1v2-2008-10
7
Installation
Minipack drawer shelf slid out in
the maintenance position
Service Loop
Cable lengths
enabling to open
the drawer shel
f
(-48V) Oute
r
Terminal
+
0V Oute
r
Terminal
Link 2 (X7A)
(DC Earth)
Common
Battery X7A
EG
Battery
Fuse, Fbx
Intercell Links
Battery
Cable
Symmetry 1
2-1
Chassis
Card Art.200576
+
-
15 pins D-Sub
(male)
Tem
p
. senso
r
Temp. Sensor cable 1
Block1
- + + - + - + -
Block4Block3
Cable lugs mounted
upside down
Common Battery
Cables (+)
Electrical Installation Power is OFF!
Carry out the following: (Refer to the next chapters “Location of
Components…” and “Connections…” or to the system’s specific drawings)
CAUTION: The cable lengths must be long enough (service loop) to allow opening the
Minipack drawer shelf.
9 Make the system completely voltage free
o Switch OFF or remove all load fuses (MCB1, MCBx), battery
fuses (Fb1, Fbx) and the AC supply fuses, in external fuse
boards
10 AC Connections
o Check AC configuration: the external AC supply consists of 3
single phase mains feed and earth (PE)
o Connect the AC Earth wires (PE) to the terminals X5:1-2 (PE)
o Connect the AC input cables to the terminals X5:3-4, 5-6, 7-8.
Cable and terminal block labeling are to correspond
o If the 3ph AC Input Connection Kit, part 228898 or 238394 is
used, follow the kit’s guide instead
11 DC Connections Load Circuits
o DC Earth (TE); check that the common DC Output Rail is
connected to “Telecom Earth” (TE) at only one place (at the
cabinet , cable X7A, or at a central distribution point)
o For each DC load, connect one of the cables to the common DC
output terminal, and the other to terminal X6B:F1, F2, etc.
12 DC Connections Alarm & Signal Circuits
o Refer to your system’s connection drawings and configuration, or
to the “Appendix, Alarms & Monitoring” section, terminal
blocks X1, X2A and or X2B.
o Terminate Alarm Circuit cables to the relay output terminals
o Terminate Signal Circuit cables to the digital input/output
terminals
13 DC Connections Battery Cables
CAREFUL! Use correct polarity.
For 48V systems using the battery symmetry mid-point
measurement, refer to the figure in this page.
For other measurement methods, refer to the Battery Symmetry
Connections chapters in this guide’s Appendix section.
For each battery shelf:
CAUTION: Mount cable lugs upside down on the (+) battery cables
a Mount 3 intercell links to connect in series 4 battery blocks
b-c Connect battery cables to fuses (Fb1, Fb2, etc.) and
Common Battery (X7A) and to the battery shelf’s outer
terminals; (+) and (-)
d-e Connect battery symmetry cables, if applicable, to the input
terminals, and to the center terminal of the battery string
(+) and to the -48V outer terminal. Deviation from factory
settings requires Symmetry reconfiguration via PowerSuite
f-g Connect the temperature sensor cable, if applicable, to the
D-Sub plug or input terminal, and fix the temperature
sensor (at the end of the cable) to a suitable place in the
middle of the installed battery bank
Electric
shock
Device
hazard

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eltek Valere Minipack and is the answer not in the manual?

Eltek Valere Minipack Specifications

General IconGeneral
BrandEltek Valere
ModelMinipack
CategoryPower Supply
LanguageEnglish

Related product manuals