User Manual QT250 and QT800, ID 2021 2.0 July 2018
Table 6: Cable requirements and recommendations for CANopen system
Cable requirements and recommendations
1 (GND) + twisted pair for CAN_H and CAN_L signals
Length related
resistance / Cross
section
Length related resistance;
typical 70 mΩ/m Max 100 m/m
70 mΩ/ 3ft 3.37 in Max 100 m/3ft 3.37 in
Normally equivalent to 0.5–1.5 mm
2
/0.02 – 0.06 in
2
Cable length (affects
communication speed)
EMC glands are not mandatory but is recommended in case
the actuator is placed in conjunction with equipment
emitting high levels of disturbances.
Nominal 120 Ω Both ends of the signal loop must have the
correct impedance. Use the internal resistor by setting the
terminal jumper in position ON, see Figure 26: CANopen
connection interface terminals on page 40.
For the analog interface, both the input and the outputs are passive. Analog has
two outputs. One Alarm output and one Position output (4 to 20 mA) (see Table
7 for details).
Table 7: Relay outputs – analog interfaces
Limiting continuous current
For the digital interface, the digital outputs are passive, and the digital inputs are
active with a 5 V/20 mA rating. The digital output must be powered (see Table 8
for details).
Table 8: Relay outputs – digital interfaces
Limiting continuous current