3.6- Connecting photocells:
Normally closed contact (when the photocells are not engaged the PHOTO LED must be on), when this input trips during closing it reverses the
movement, if not used then jumper between COM and PHOTO, you must observe the polarity of the power supply for the photocells:
3.7- Sensitive edge connection
Programmable input (with the edge or photocell not engaged, the STPA LED must be on) if this input trips during opening it immediately reverses the
movement for 1.5 seconds and then stops the gate, while during closure it reverses the movement until fully open, see the dip switch 1-4 to select the
type of edge. If not used jumper between COM. and STPA and set the dip switch 1-4 off:
STPA input as edge with
electromechanical switch, set the
dip switch 1-4 OFF
STPA input as edge
resistive 8.2Kohm, set the dip
switch 1-4 ON
Switch edge connectionResistive sensitive edge connection
8.2 KΩ
Fig. 9
3.8- Electrical connection with photo-test function active (dip switch 1-3 and 1-8 ON) the control unit governs the operation of the safety
devices.
DIP 1
DIP 2
DIP 1
DIP 2
Example DIP en ON
position:
Example DIP en
OFF position:
COM
STPA
COM
STPA
Fig. 8
1 2 3 4 5 6 7 8
RX1
+-CNCN