4 Physical installation
4.1 Pipe mount
Tools needed:
• 2-in. (51 mm) mounting pipe or mast
• Two 5/16-in. (7,9 mm) u-bolts supplied with Gateway
• 1/2-in. socket-head wrench
For installing the Gateway with a pipe mount:
Procedure
1. Insert one u-bolt around the pipe, through the top mounting holes of
the Gateway enclosure, and through the washer plate.
2. Use a 1/2-in. socket-head wrench to fasten the nuts to the u-bolt.
3. Repeat Step 1 and Step 2 for the second u-bolt and lower mounting
holes.
4.1.1 Best practice
If the Gateway was ordered with output code 2, run a secondary Ethernet
cable when installing cable conduit from the Gateway to a convenient
indoor location to simplify future configuration changes.
4.2
Remote antenna (optional)
The remote antenna options provide flexibility for mounting the Gateway
based on wireless connectivity, lightning protection, and current work
practices.