Service Instructions
137462E Rev. D
6
Section 1: Introduction
Introduction
1.11.5 Due to the interaction of these variables, it is difcult to specify a "normal"
operating time. Faster operating time may be obtained by using one or more of
the following:
1. Larger supply lines
2. Larger control valve
3. Higher supply pressure *
4. Quick exhaust valves
* Not to exceed maximum operating pressure of actuator or
control components
1.11.6 Slower operating time may be obtained by using ow control valves to meter the
exhaust. Excessive exhaust ow metering may cause erratic operation.
1�12 Actuator Operation
1.12.1 Controlled Operation: Controlled operation is accomplished by pressurizing and/
or depressurizing the appropriate cylinder inlet(s) of a double-acting. Do not
exceed pressures indicated on actuator nameplate.
1.12.2 Manual Operation: All pressure must be vented or equalized on both sides of the
pneumatic piston prior to manual operation.