EasyManua.ls Logo

Emerson Comfort Alert 543-0033-00 - Comfort Alert Diagnostics Module; Module Overview and Benefits; LED Indicator Functions; Product Specifications

Emerson Comfort Alert 543-0033-00
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2
Comfort Alert™
Diagnostics – Faster Service And Improved Accuracy
heat pump and air conditioning system failures. The module installs easily in the electrical
box of the outdoor unit near the compressor contactor. By monitoring and analyzing
data from the Copeland Scroll
®
compressor and the thermostat demand, the module
can accurately detect the cause of electrical and system related failures without any
sensors. A ashing LED indicator communicates the ALERT code and guides the service
technician more quickly and accurately to the root cause of a problem.
NOTE:
This module does not provide safety protection! The Comfort Alert module
is a monitoring device and cannot shut down the compressor directly.
LED Description (Figure 1)
POWER LED (Green): indicates voltage is present at
the power connection of the module.
ALERT LED (Yellow): communicates an abnormal system
condition through a unique ash code. The ALERT LED
will ash a number of times consecutively, pause and then
repeat the process. The number of consecutive ashes,
de ned as the Flash Code, correlates to a particular
abnormal condition. Detailed descriptions of specific
ALERT Flash Codes are shown in two tables on pages 8
and 9 of this manual.
TRIP LED (Red): indicates there is a demand signal from
the thermostat but no current to the compressor is detected
by the module. The TRIP LED typically indicates the
compressor protector is open or may indicate
missing supply power to the compressor.
Product Specifi cations
Operating Temperature: -40° to 150° F (-40° to 65° C)
Storage Temperature: -40° to 175° F (-40° to 80° C)
Power Supply Range: 18-30VAC, 48-62 Hz
Power Requirement: 1.5 VA nominal (without solenoid on)
6.0VA nominal (with solenoid on)
UL Restrictions: Use only with Class 2 circuits.
scroll compressors that have internal overload protection.
The software in this Comfort
Alert module has been optimized for two stage UltraTech™ scroll systems.
Figure 1
UL File #SA8958

Related product manuals