102
Epsilon Eb and EN Drives Reference Manual
Figure 73: EN Input/Output Wiring Diagram
Figure 74: Epsilon Input/Output Wiring Diagram
Front View
I/O supply
+10 to 30 VDC
2.8 k
Load
Load
Load
A
highspeed diode
(such as a 1N5819) is
required for inductive
loads such as a relay,
solenoid or contactor.
J6
-
+
24 VDC
1 Amp Fuse
Single point
PE ground.
Drive Enable Input
10
Input #4
Input #3
Input #2
Input #1
11
1
2
12
8
Output #3
Output #2
Output #1
7
17
I/O Supply +
I/O Common -
19
20
Front View
Single point
PE ground.
-
+
24 VDC
Load
Load
Load
A
highspeed diode
(such as a 1N5819) is
required for inductive
loads such as a relay,
solenoid or contactor.
I/O supply
+10 to 30 VDC
2.8 k
J3
1 Amp Fuse