AGL_Stream_ST_A2L_A1_4M_6M_EN_Rev00 11
3 Installation
WARNING
High pressure! Injury to skin and eyes possible! Be careful when opening
connections on a pressurized item.
3.1 Compressor handling
3.1.1 Delivery
Please check whether the delivery is correct and complete. Any deficiency should be reported
immediately in writing. Standard delivery:
Suction and discharge shut-off valves (service compressor 4M*S and 6M*S have blind flanges
instead of shut-off valves)
Oil charge, oil sight glass
Mounting kit
Copeland compressor electronics module
Holding charge up to 2.5 bar(g) (dry air)
Compressors are delivered on pallets. Cooling fans are delivered in separate boxes. Accessories
may be mounted or delivered loose. Solenoid valves are never mounted.
3.1.2 Transport and storage
Respect the maximum number of identical packages which may be stacked on one another,
where "n" is the limiting number:
Transport: n = 1
Storage: n = 1
Figure 12: Maximum stacking loads for transport and storage
NOTE: The compressor is pre-charged with dry air to avoid any moisture contamination.
3.1.3 Positioning and securing
If possible, the compressor should be kept horizontal during handling.
For safety reasons two lifting eyes should be fitted before moving a compressor (½" - 13 UNC).
Otherwise refer to drawings in Figure 13 to see how to apply other lifting methods.
4M* 6M*
max. 220 kg max. 260 kg
Figure 13: Compressor lifting methods