6 AGL_Stream_ST_A2L_A1_4M_6M_EN_Rev00
2.5.3 Liquid injection / Demand cooling
"Demand Cooling" as the term implies means liquid refrigerant injection on demand.
Liquid injection may be required for low temperature applications in order to keep the compressor
within safe discharge temperature limits. The liquid injection system consists of an electronic
expansion valve with a solenoid coil, controlled by the Copeland compressor electronics system
(dedicated "Liquid injection" extension module C to be ordered).
For low temperature applications with R454C, R455A and R454A, liquid injection can be required on
the following compressors:
4MF-13X 4ML-15X 4MM-20X 4MT-22X 4MU-25X
6MM-30X 6MT-35X 6MU-40X
NOTE: For corresponding application envelopes, please see Select software available at
www.climate.emerson.com/en-gb.
2.5.4 Unloaded start
Unloaded start is mainly required for compressors connected for part-winding start (for example with
motor version AWM) or star-delta start (motor version EWM).
4M* and 6M* compressors can be equipped with an internal unloaded start system, to be ordered as
an option. The compressor prepared for unloaded start is supplied with a special cylinder head. The
control valve and coil are positioned on the top of the cylinder head. An additional check valve must
be installed in the discharge piping. Recommended inbuild position for the check valve is
approximately 50-100 cm to the compressor discharge connection.
Usually, the unloaded start is activated once for about 5-10 seconds shortly before compressor start
and then kept closed during operation. The unloaded start solenoid valve opens a suction channel
in the valve plate and the pressure in the discharge line equalizes to the suction side.
A. Standard operation B. Unloaded start operation
Figure 3
1 Special cylinder head
2 Solenoid
3 Valve
4 Spring-loaded control piston
5 Suction side
6 High side in the cylinder head
7 Valve plate
1
6
5
2
3
4
7