14 AGL_Stream_ST_A2L_A1_4M_6M_EN_Rev00
3.3 Brazing procedure
Refer to Figure 15 and procedure below for the brazing of the suction and discharge lines:
Flushing oxygen-free nitrogen through the piping
during the brazing process is recommended for
applications with A1 refrigerants and mandatory for
applications with flammable A2L refrigerants.
The copper-coated steel tubes on Stream
compressors can be brazed in approximately the same
manner as any copper tube.
Recommended brazing material: any Silfos
material is recommended, preferably with a minimum of
5% silver. However, 0% silver is acceptable. For brazing
connections where dissimilar or ferric metals are joined a silver alloy rod with a minimum silver
content of 30 % shall be used being either flux-coated or with a separate flux.
Be sure tube fitting inner diameter and tube outer diameter are clean prior to assembly.
Using a double-tipped torch, apply heat in area 1.
As the tube approaches brazing temperature, move the torch flame to area 2.
Heat area 2 until braze temperature is attained, moving the torch up and down and rotating around
the tube as necessary to heat the tube evenly. Add braze material to the joint while moving the
torch around the joint to flow braze material around the circumference.
After the braze material flows around the joint, move the torch to heat area 3. This will draw the
braze material down into the joint. The time spent heating area 3 should be minimal.
As with any brazed joint, overheating may be detrimental to the final result.
3.4 Filter screens
CAUTION
Screen blocking! Compressor breakdown! Use screens with at least
0.6 mm openings.
The use of screens finer than 30 x 30 meshes (0.6 mm openings) anywhere in the system should be
avoided with these compressors. Field experience has shown that finer mesh screens used to protect
thermal expansion valves, capillary tubes or accumulators can become temporarily or permanently
plugged with normal system debris and block the flow of either oil or refrigerant to the compressor.
Such blockage can result in compressor failure.
Figure 15: Brazing areas