EasyManua.ls Logo

Emerson Copeland 4MF-13X - Low-Pressure Protection; Maximum Allowable Pressures

Emerson Copeland 4MF-13X
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AGL_Stream_ST_A2L_A1_4M_6M_EN_Rev00 13
3.2.2 Low-pressure protection
3.2.2.1 Applications with A1 refrigerants
Applicable regulations and standards shall be followed to apply appropriate control and ensure that
the pressure is always above the required minimum limit.
The low-pressure control must be installed correctly into the suction line, which means that no service
valve is allowed between the compressor and the pressure protection.
The minimum cut-out setting shall be determined according to the refrigerant and the allowed
operation envelope see Select software at www.climate.emerson.com/en-gb.
The low-pressure cut-out should have a manual reset feature for the highest level of system
protection.
3.2.2.2 Applications with A2L refrigerants
Make sure that the pressure never falls below atmospheric pressure. If it does, immediately de-
energize the power supply of the compressor and check the cause of the low pressure before
restarting the compressor.
Emerson requires without exception that all 4M* and 6M* compressors in A2L systems be fitted with
a low-pressure control, with no service valve between the low pressure side and the pressure control.
3.2.3 Maximum allowable pressures
The maximum allowable pressures according to EN 12693 shown on the compressor nameplate are
obligatory and must not be exceeded.
High-pressure side (HP): 28.0 bar (g) (up to S/N 14K46143M)
32.5 bar (g) (from S/N 14K46144M onwards)
Low-pressure side (LP): 22.5 bar
NOTE: The compressor operating range may be restricted for various reasons. Check the
application range limitations in Select software at www.climate.emerson.com/en-gb.

Table of Contents

Other manuals for Emerson Copeland 4MF-13X

Related product manuals